Application Guide

SAG582140000 System Application Guide
Issue AW, June 3, 2014 Spec. No. 582140000 (Models 802
NLDB, 802NLEB and 802NL-B)
Page 48 of 134
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Ampere
Rating
Number of Poles
(and mounting positions
required in Bullet Nose-Type
Circuit Breaker/Fuseholder
Mounting Assembly)
Part Number
Electrical Trip
1
(White Handle)
Electrical/
Mechanical Trip
2
(Black Handle)
1 1 142856 142878
3 1 142857 142879
5 1 142858 142880
10 1 142859 142881
15 1 142861 142882
20 1 142862 142883
25 1 142863 142884
30 1 142864 142885
35 1 142865 142886
40 1 142866 142887
45 1 142867 142888
50 1 142868 142889
60 1 142869 142890
70 1 142870 142891
75 1 142871 142892
80 1 142872 142901
100 1 142873 142902
125 2 142874 142903
150 (see
Caution
below) 2 142875 142904
200 (see
Caution
below) 2 142876 142905
Order a Bullet Nose-Type Circuit Breaker/Fuseholder Mounting Assembly, P/N 513747, for every six circuit
breaker/fuseholder combinations ordered. Each bullet nose-type circuit breaker/fuseholder mounting
assembly requires six (6) distribution bus mounting positions.
See Table 9 for recommended load distribution wire sizes and lugs.
Circuit Breaker Alarm Operation:
1
Provides an alarm during an electrical trip condition only.
2
Provides an alarm during an electrical or manual trip condition.
Caution: An overcurrent protective device with a rating of 150 amperes or greater SHALL HAVE an
empty mounting position between it and any other overcurrent protective device within the
circuit breaker/fuseholder mounting assembly.
Table 4
Rocker-Handle Bullet Nose-Type Circuit Breakers and Bullet Nose-Type
Circuit Breaker/Fuseholder Mounting Assembly
Home