Application Guide

SAG582140000 System Application Guide
Issue AW, June 3, 2014 Spec. No. 582140000 (Models 802
NLDB, 802NLEB and 802NL-B)
Page 46 of 134
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Bullet Nose-Type Circuit Breakers and
Bullet Nose-Type Circuit Breaker/Fuseholder Mounting AssemblyPower/Distribution Bays
Features
Each bullet nose-type circuit breaker/fuseholder mounting assembly can mount up to six (6) bullet nose-
type circuit breakers and/or fuseholders.
Each bullet nose-type circuit breaker/fuseholder mounting assembly is equipped with a shunt for MCA
load current measurements (one shunt per six bullet nose-type devices).
Bolts into bay's distribution device mounting positions.
Load lugs are connected to the existing load busbars provided at the top of the Power/Distribution Bay.
These busbars provide 1/4-20 studs on 5/8" centers and hardware for installation of customer provided
two-hole lugs. For load return lug requirements, refer to Power/Distribution and Power Only Bays
External Busbars in this section.
Restrictions
Load should not exceed 80% of device rating.
Each bullet nose-type circuit breaker/fuseholder mounting assembly requires six (6) distribution bus mounting
positions.
Each distribution bus is divided into half. Each half MUST be populated with distribution devices from left-to-
right, without skipping any distribution device mounting positions within each half.
Bullet nose-type circuit breaker/fuseholder mounting assembly rated for 480 amperes, maximum.
Caution: An overcurrent protective device with a rating of 150 amperes or greater SHALL HAVE an
empty mounting position between it and any other overcurrent protective device within the
circuit breaker/fuseholder mounting assembly.
Refer to the illustrations at the beginning of this section for maximum size of wire to be connected to a single
lug position and maximum lug width.
Ordering Notes
1) Order circuit breakers per Table 3 and Table 4.
2) Order a Bullet Nose-Type Circuit Breaker/Fuseholder Mounting Assembly, P/N 513747, for every six
circuit breaker/fuseholder combinations ordered.
3) See Table 9 for recommended load distribution wire sizes and lugs.
Home