List 66: Interface Kit to a Vortex Power System without a DGU or LMS1000
Features
Provides the following...
LMS Dual MCA Interface Software Option
P/N 526843 50’ LMS Dual MCA Option Cable
LMS Dual MCA Interface Software Option enables the Spec. No. 582140000 Power System to be
integrated with an existing Power System. Specifically, List 66 allows the MCA in Spec. No. 582140000
to interface with the MCA in a Vortex Power System via the LMS in Spec. No. 582140000. Refer to the
LMS documentation for further information.
Restrictions
Operation of Energy Management is disabled with this option installed.
Ordering Notes
1) Order as required.
List 67: Interface Kit to a Model 1231H Legacy Power System with 1-8 Rectifiers
Features
Provides the following...
LMS Gateway Software Option
P/N 548009 50’ LMS Gateway Port Cable
Two (2) P/N 506336 LMS 4-Input Universal Analog Cards
One (1) P/N 506334 LMS 8-Input Binary Card
LMS Gateway Software Option allows the LMS to emulate a “dumb” RS-232 asynchronous terminal
interface. Specifically, List 67 enables user input through either a local or remote LMS port to be directed
to a DGU (in the legacy plant) connected to the LMS Gateway port. Refer to the LMS documentation for
further information.
The analog and binary DGU I/O cards provide monitoring of the legacy system’s rectifiers
Restrictions
LMS Channels must be configured.
Ordering Notes
1) Order as required.
List 70: Additional MCA Six (6) Output Form-C Relay Circuit Card
Features
Provides six relays each with one set of Form-C relay contacts.
These relays are used for alarm applications and can be programmed by the user.
Refer to the "Specifications" section of this document for further information.
Plugs into any slot in 7-position card cage in Primary and Secondary Power/Distribution and Power Only
Bays.
User maps relay closure to any or multiple programmable alarm functions.
Restrictions
Relay contacts rated for 2A at 30 volts DC.
The system may contain up to 16 MCA Relay circuit cards.
Ordering Notes
1) List 1, 2, 3, 4, and 5 each include two (2) relay cards, order List 70 for additional cards if necessary.
2) Order one (1) List 70 relay circuit card for every six (6) customer relay contacts to be provided by the
MCA.