Application Guide

SAG582140000 System Application Guide
Issue AW, June 3, 2014 Spec. No. 582140000 (Models 802
NLDB, 802NLEB and 802NL-B)
Page 26 of 134
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Restrictions
For use with List 30 or List 31 manufactured after 12/01/04 only.
See Surge Protection in the SPECIFICATION section for additional ratings.
Ordering Notes
1) Order if additional surge suppression is required.
2) A wire harness is factory connected to Form-C relay contacts located on each surge suppression
assembly for remote monitoring. Connect the wire harness to the first two binary inputs on an MCA I/O
circuit card (separately ordered See List 71). The MCA then provides alarm display messages and an
audible alarm when a surge suppression assembly activates. Order a List 71 MCA I/O Circuit Card as
required to provide MCA binary inputs for the surge suppression alarms.
3) Note that two (2) MCA customer alarm relay circuit cards are provided with the primary bay. If remote
surge suppression alarm relay contacts are required and you expect to use the alarm relays on the
factory provided cards for other uses, order a List 70 MCA relay circuit card as required.
List 36: Surge Suppression for 208VAC Input PDSC
Features
Provides two (2) surge suppression assemblies for the PDSC. One wired to Rectifier AC input circuit
breakers CB1, CB3, CB5, CB7, and CB9. The other to CB2, CB4, CB6, CB8, and CB10.
100kA interrupting capacity.
Overcurrent fusing and thermal protection.
Restrictions
For use with List 32 only.
See Surge Protection in the SPECIFICATION section for additional ratings.
Ordering Notes
1) Order if additional surge suppression is required.
2) A wire harness is factory connected to Form-C relay contacts located on each surge suppression
assembly for remote monitoring. Connect the wire harness to the first two binary inputs on an MCA I/O
circuit card (separately ordered See List 71). The MCA then provides alarm display messages and an
audible alarm when a surge suppression assembly activates. Order a List 71 MCA I/O Circuit Card as
required to provide MCA binary inputs for the surge suppression alarms.
3) Note that two (2) MCA customer alarm relay circuit cards are provided with the primary bay. If remote
surge suppression alarm relay contacts are required and you expect to use the alarm relays on the
factory provided cards for other uses, order a List 70 MCA relay circuit card as required.
List 37: Surge Suppression for 208VAC Input
Features
Provides two (2) surge suppression assemblies for the Power Only Bay. One wired to Rectifier AC input
circuit breakers CB1, CB3, CB5, CB7, and CB9. The other to CB2, CB4, CB6, CB8, and CB10.
100kA interrupting capacity.
Overcurrent fusing and thermal protection.
Restrictions
For use with List 4 and 14.
See Surge Protection in the SPECIFICATION section for additional ratings.
Ordering Notes
1) Order if additional surge suppression is required.
2) A wire harness is factory connected to Form-C relay contacts located on each surge suppression
assembly for remote monitoring. Connect the wire harness to the first two binary inputs on an MCA I/O
Home