Application Guide

System Application Guide SAG582140000
Spec. No. 582140000 (Models 802
NLDB, 802NLEB and 802NL-B) Issue AW, June 3, 2014
Page 21 of 134
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Restrictions
Requires List 30 (480VAC Input), List 31 (480VAC Input), or List 32 (208VAC Input) Bolt-On PDSC
(AC Input 'Power Distribution Service Cabinet').
Maximum of nine (9) Secondary Power/Distribution Bays per power system.
Ordering Notes
1) Specify List A (480VAC Input) or List B (208VAC Input).
2) Order Bolt-On PDSC (AC Input 'Power Distribution Service Cabinet') per List 30 (480VAC Input), List 31
(480VAC Input), or List 32 (208VAC Input).
3) Order Rectifiers as required per P/N 486532602 or P/N 486532603 (480VAC Input) or P/N 486534003
(208VAC Input).
4) Order distribution fuse and/or circuit breaker devices as required per Distribution Devices in the
ACCESSORY DESCRIPTIONS section.
5) Order additional MCA customer alarm relay circuit card(s) as required per List 70, and optional MCA I/O
circuit cards per List 71.
6) Order optional LMS Expansion CPU circuit card and LMS options as required per List 63, and
SAG586505000. Also order additional LMS Network cables as required per Replacement/Additional LMS
Network Cables.
7) Order bay grounding lugs as required per Power/Distribution Bay Frame Grounding Wire Sizes and Lugs
in the ACCESSORY DESCRIPTIONS section.
8) Order load distribution lugs as required per Power/Distribution Bay and Distribution Only Bay Load
Distribution Wire Sizes and Lugs in the ACCESSORY DESCRIPTIONS section.
9) Order battery cable lugs as required per Power/Distribution Bay Battery Cable Sizes and Lugs in the
ACCESSORY DESCRIPTIONS section.
10) Order AC input lugs as required per Power/Distribution Bay AC Input, Two (2) Rectifier Feeds Wire Sizes,
Branch Circuit Protection, and Lugs or Power/Distribution Bay AC Input, One (1) Rectifier Feed Wire
Sizes, Branch Circuit Protection, and Lugs in the ACCESSORY DESCRIPTIONS section.
11) Order internal ground busbar assembly, external top-mount battery input busbar assembly, busbar shield
kit, external top-mount ground (load return) busbar assembly, and/or load return lug extension busbar
assembly as required per the appropriate sections located under ACCESSORY DESCRIPTIONS.
12) If Secondary Bays are placed on both sides of the Primary Bay, a different length MCA Network cable is
required that connects a Secondary Bay on one side with a Secondary Bay on the other side. Order per
Replacement/Additional MCA Network Cables. Refer to the Installation Instructions (Section 5876) for
bay line-up and MCA Network cabling requirements.
13) Side cover panels are provided with Primary Bays. These cover panels are used with Secondary Bays
when bays are placed next to each other. In installations where a Secondary Bay is placed by itself,
order (1) of each of the following side cover panels per exposed side: P/N 514482 and P/N 514484.
List 13: Secondary Power Only Bay, Five (5) AC Feeds (Common Equipment)
Features
Provides common equipment for one (1) power only bay rated for up to 2200 amperes.
Mounted in a 7’0”H x 24"W x 30"D box framework.
Provides ten (10) Rectifier mounting positions.
Provides AC input circuit breakers rated for 22kA interrupting capacity for each rectifier position. Circuit
breakers are pad-lockable.
In ferro replacement applications, will accommodate five (5) AC inputs sized for 400A ferro rectifiers
(208V, 100A or 480V, 50A).
Provides the Router Assembly.
Provides mounting for optional LMS Expansion CPU circuit card.