Application Guide
System Application Guide SAG582140000
Spec. No. 582140000 (Models 802
NLDB, 802NLEB and 802NL-B) Issue AW, June 3, 2014
Page 17 of 134
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
12) Order internal ground busbar assembly, external top-mount battery input busbar assembly,
busbar shield kit, external top-mount ground (load return) busbar assembly, and/or load return
lug extension busbar assembly as required per the appropriate sections located under ACCESSORY
DESCRIPTIONS.
13) If the system is to be connected to an existing system with an MCA, refer to List 64, 65, 66, and 67.
List 3: Primary Power Only Bay, Five (5) AC Feeds (Common Equipment)
Features
♦ Provides common equipment for one (1) power only bay rated for up to 2200 amperes.
♦ Mounted in a 7’0”H x 24"W x 30"D box framework.
♦ Provides ten (10) Rectifier mounting positions.
♦ Provides AC input circuit breakers rated for 22kA interrupting capacity for each rectifier position. Circuit
breakers are pad-lockable.
♦ In ferro replacement applications, will accommodate five (5) AC inputs sized for 400A ferro rectifiers
(208V, 100A or 480V, 50A).
♦ Provides the MCA Assembly and Local MCA Control Panel.
♦ Provides mounting for optional LMS Main CPU circuit card.
♦ Provides a seven-slot card cage for mounting MCA customer alarm relay circuit cards, MCA I/O circuit
cards, and/or optional LMS I/O circuit cards. Two (2) MCA customer alarm relay circuit cards provided.
♦ Expandable either left or right, cable connected.
Restrictions
Only one (1) Primary Bay per power system required.
Requires external main battery termination bars.
Ordering Notes
1) Specify List A (480VAC Input) or List B (208VAC Input).
2) If List A specified, order ten (10) P/N 256933200 30A circuit breakers.
3) If List B specified, order ten (10) P/N 256937200 60A circuit breakers.
4) Order Rectifiers as required per P/N 486532602 or P/N 486532603 (480VAC Input) or P/N 486534003
(208VAC Input).
5) Order additional MCA customer alarm relay circuit card(s) as required per List 70, and optional MCA I/O
circuit cards per List 71.
6) Order a Battery Charge Temperature Compensation Probe as required per Battery Charge Temperature
Compensation Probe for Digital Compensation in the ACCESSORY DESCRIPTIONS section.
7) Order optional LMS Monitor and LMS options as required per List 50, and SAG586505000.
8) Order bay grounding lugs as required per Power Only Bay Frame Grounding Wire Sizes and Lugs in the
ACCESSORY DESCRIPTIONS section.
9) Order DC output cable lugs as required per Power Only Bay DC Output Cable Sizes and Lugs in the
ACCESSORY DESCRIPTIONS section.
10) Order AC input lugs as required per Power Only Bay AC Input, Five (5) Rectifier Feeds Wire Sizes,
Branch Circuit Protection, and Lugs in the ACCESSORY DESCRIPTIONS section.
11) Order external top-mount battery input busbar assembly, busbar shield kit, external top-mount ground
(load return) busbar assembly, and/or load return lug extension busbar assembly as required per the
appropriate sections located under ACCESSORY DESCRIPTIONS.
12) If the system is to be connected to an existing system with an MCA, refer to List 64, 65, 66, and 67.