Application Guide

System Application Guide SAG582140000
Spec. No. 582140000 (Models 802
NLDB, 802NLEB and 802NL-B) Issue AW, June 3, 2014
Page 15 of 134
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
LIST DESCRIPTIONS
List A: 480VAC Plant Input Voltage
Features
Specifies 480VAC Plant Input Voltage.
List B: 208VAC Plant Input Voltage
Features
Specifies 208VAC Plant Input Voltage.
List 1: Primary Power/Distribution Bay (Common Equipment)
Features
Provides common equipment for one (1) “power and distribution” bay rated for up to 2400 amperes.
Mounted in a 93.5"H x 24"W x 30"D box framework.
Provides ten (10) Rectifier mounting positions.
Provides an AC input termination panel that accepts ten (10) AC input branch circuits, one (1) per
Rectifier mounting position.
Provides forty-eight (48) distribution device mounting positions.
Provides two (2) buses of distribution. Each bus contains an MCA monitoring circuit card; which can be
set for no group designation, Group A designation, or Group B designation.
Configured for a 4000A internal bus or external main battery termination bars.
Provides the MCA Assembly and Local MCA Control Panel.
Provides mounting for optional LMS Main CPU circuit card.
Provides a seven-slot card cage for mounting MCA customer alarm relay circuit cards, MCA I/O circuit
cards, and/or optional LMS I/O circuit cards. Two (2) MCA customer alarm relay circuit cards provided.
Expandable either left or right.
Restrictions
Only one (1) Primary Bay per power system required.
Ordering Notes
1) Specify List A (480VAC Input) or List B (208VAC Input).
2) Order Rectifiers as required per P/N 486532602 or P/N 486532603 (480VAC Input) or P/N 486534003
(208VAC Input).
3) Order distribution fuse and/or circuit breaker devices as required per Distribution Devices in the
ACCESSORY DESCRIPTIONS section.
4) Order additional MCA customer alarm relay circuit card(s) as required per List 70, and optional MCA I/O
circuit cards per List 71.
5) Order a Battery Charge Temperature Compensation Probe as required per Battery Charge Temperature
Compensation Probe for Digital Compensation in the ACCESSORY DESCRIPTIONS section.
6) Order optional LMS Monitor and LMS options as required per List 50, and SAG586505000.
7) Order bay grounding lugs as required per Power/Distribution Bay Frame Grounding Wire Sizes and Lugs
in the ACCESSORY DESCRIPTIONS section.
8) Order load distribution lugs as required per Power/Distribution Bay and Distribution Only Bay Load
Distribution Wire Sizes and Lugs in the ACCESSORY DESCRIPTIONS section.
9) Order battery cable lugs as required per Power/Distribution Bay Battery Cable Sizes and Lugs in the
ACCESSORY DESCRIPTIONS section.
10) Order AC input lugs as required per Power/Distribution Bay AC Input, Ten (10) Rectifier Feeds Wire
Sizes, Branch Circuit Protection, and Lugs in the ACCESSORY DESCRIPTIONS section.