Application Guide
System Application Guide SAG582140000
Spec. No. 582140000 (Models 802
NLDB, 802NLEB and 802NL-B) Issue AW, June 3, 2014
Page 107 of 134
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
3.4.4 Typical Input Data: 60 Hz input.
(A) System output is initially adjusted to 54.48 volts DC as measured at the output bus at 50%
of full load and nominal input.
Number
of
Rectifiers
Installed
Nominal
Input
Voltage
Percent
of Full
Load
Input
Current
(Amperes)
Input
VA
Input
Watts
Power
Factor
Efficiency
%
1 208
0
0.692
40.8
6.69
0.164
--
25 8.196 2883 .2811 0.975 94.7
50
15.897
5688
.5648
0.993
95.7
75 23.900 8571 8537 0.996 95.3
100
32.140
11519
11496
0.998
94.5
(B) Typical Efficiency versus Output Current:
(C) Maximum input current at 100% of full load with output adjusted to 58 volts DC as
measured at the output bus.
Nominal
Input
Voltage
Input
Voltage
Number of
Rectifiers
Installed
Input Current
(Amperes)
208 208
1 34.25
2
68.50
3 103.75
4
138.00
5 172.25
6
206.75
7 241.00
8
275.25
9 309.50
10
343.75
3.5 Standard Features
3.5.1 Type of Power Conversion Circuit: High frequency.
3.5.2 Float Charging Output Mode: In this mode of operation, system output voltage is constant
and output current does not exceed the current limit setting. During normal operation, the
battery is not required to furnish load current and remains in a fully charged condition.