Application Guide

System Application Guide SAG582140000
Spec. No. 582140000 (Models 802
NLDB, 802NLEB and 802NL-B) Issue AW, June 3, 2014
Page 105 of 134
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
(C) Maximum input current at 100% of full load with output adjusted to 58 volts DC as
measured at the output bus.
Nominal
Input
Voltage
Input
Voltage
Number of
Rectifiers
Installed
Input Current
(Amperes)
480 408
1
17.83
2 35.67
3
53.50
4 71.34
5
89.17
6 107.00
7
124.84
8 142.67
9
160.51
10 178.34
3.3 Input Ratings (480VAC, with 486532603 Rectifier)
3.3.1 Voltage: Nominal 480 volts AC, three phase, 60 Hz, with an operating range of 340 to 528
volts. Acceptable input frequency range is 57 to 63 Hz.
3.3.2 Harmonic Content: Complies with IEEE-519-1992. Voltage harmonic distortion of less than
5% at nominal input when operating on a line impedance of 0.104 ohms or less.
3.3.3 Inrush Current: Peak does not exceed 6 times the RMS input current at full load, under any
conditions of input voltage within the rated input voltage range stated in Paragraph 3.3.1 and
for any duration of AC input interrupts. Under the above conditions, standard AC distribution
circuit breakers will not trip.
3.3.4 Typical Input Data: 60 Hz input.
(A) System output is initially adjusted to 54.48 volts DC as measured at the output bus at 50%
of full load and nominal input.
Number
of
Rectifiers
Installed
Nominal
Input
Voltage
Percent
of Full
Load
Input
Current
(Amperes)
Input
VA
Input
Watts
Power
Factor
Efficiency
%
1 480
0 1.35 1122 0 0.074 --
25
3.78
3147
2713
0.908
94.0
50 6.99 5813 5429 0.973 95.9
75
10.30
8563
8120
0.987
96.1
100 13.66 11358 10797 0.992 95.9