Application Guide

SAG582140000 System Application Guide
Issue AW, June 3, 2014 Spec. No. 582140000 (Models 802
NLDB, 802NLEB and 802NL-B)
Page 104 of 134
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
3.2.4 Typical Input Data: 60 Hz input.
(A) System output is initially adjusted to 54.48 volts DC as measured at the output
bus at 50% of full load and nominal input.
Number
of
Rectifiers
Installed
Nominal
Input
Voltage
Percent
of Full
Load
Input
Current
(Amperes)
Input
VA
Input
Watts
Power
Factor
Efficiency
%
1 480
0
1.38
1143
170
0.149
--
25 4.12 3420 3077 0.899 88.9
50
7.27
6046
5889
0.974
92.3
75 10.72 8901 8838 0.993 92.6
100
14.25
11851
11807
0.996
92.3
(B) Typical Efficiency versus Output Current:
76.00
78.00
80.00
82.00
84.00
86.00
88.00
90.00
92.00
94.00
0.000 50.000 100.000 150.000 200.000 250.000
Percent Efficiency
Output Current (Amps)
Typical Efficiency versus Output Current
480V
408
528