1.2.6 Heat Dissipation: With R48-12000e Rectifier(s) output adjusted to 54.48 volt DC at
rated full load and nominal input voltage.
R48-1200e Rectifier (P/N 486532603)
No. of
Rectifiers
Bay Output Current
(Amperes)
BTU/Hr
(Typical)
1 0 (Rectifier no load) 390
1 100 (Rectifier half load)
800
1 200 (Rectifier full load) 1568
2 400 3136
3 600 4704
4 800 6272
5 1000 7840
6 1200 9408
7 1400 10976
8 1600 12544
9 1800 14112
10 2000 15680
1.2.7 Heat Dissipation: With R48-12000Le Rectifier(s) output adjusted to 54.48 volt DC at rated full
load and nominal input voltage.
R48-12000Le Rectifier P/N 486534003
No. of
Rectifiers
Bay Output Current
(Amperes)
BTU/Hr
(Typical)
1
0 (Rectifier no load)
--
1
100 (Rectifier half load)
--
1
200 (Rectifier full load)
2404
2
400
4608
3
600
6912
4
800
9216
5
1000
11520
6
1200
13824
7
1400
16128
8
1600
18432
9
1800
20736
10
2000
23040
1.2.8 Ventilation Requirements: The Rectifiers are fan cooled and utilize front to back forced
ventilation. The Power/Distribution Bays and Power Only Bay must be mounted so ventilating
openings are not blocked and temperature of the air entering the Rectifier shelf does not
exceed the Operating Ambient Temperature Range stated above.
Also, the distance from the rear of a Power/Distribution Bay or Power Only Bay to a wall or
other solid structure must not be less than 6 inches. This will assure proper air flow through
the Rectifiers.