Application Guide

System Application Guide SAG582120600
Spec. No. 582120600 (Model 801DB
NVGB) Issue BF, February 21, 2014
Page 67 of 72
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
1.6 Standard FeaturesLists 106 and 108
1.6.1 Fuse/Circuit Breaker Mounting Positions: See description in Distribution Panel
List Options section.
1.6.2 External Alarm Circuits: Four (4) relays each provide three (3) sets of Form-C contacts for
external alarms. Various available alarms can be mapped to each of the relays. Contact rating
is 2A at 30 VDC.
1.6.3 Local Controls and Indicators: A status indicator at the top of the bay front panel indicates
system status. The Meter/Alarm Panel provides digital metering of load voltage and current
individually for each distribution panel. Also displays system alarm messages and adjustment
information.
1.6.4 Meter Accuracy
(A) Current: ±1.0%
(B) Voltage: ±0.1%
1.6.5 Remote Access: Via Web Interface
(A) Description: The Web Interface provides remote access to the system monitoring and
control functions that are available locally at the Meter/Control Panel.
(B) Connection: Ethernet, RJ 45 10BaseT jack. This jack has a standard Ethernet pin
configuration scheme, twisted pair. Use shielded Ethernet cable, grounded at both ends.
(The Meter/Alarm Panel’s RJ-45 jack is connected to chassis ground.) The Ethernet port is
suitable for connection to intra-building or non-exposed wiring or cabling only.
(C) Users: 64, maximum
(D) Security:
(1) Password Protection: When logging onto the system, the user is prompted to enter a
"User Password".
(2) Page Access Levels: User configurations provide a "Page Access Level" which can be
used to limit the functions available to a particular user. Eight Page Access Levels are
available.
(E) PC Requirements:
(1) Web Browser: Microsoft® Internet Explorer 5.0 or newer is required.
(2) Screen Resolution: 1024 x 768 or greater is required.
Home