Application Guide
SAG582120600 System Application Guide
Issue BF, February 21, 2014 Spec. No. 582120600 (Model 801DB
NVGB)
Page 66 of 72
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SPECIFICATIONS
1.1 DC Operating Voltage
1.1.1 Nominal: -48Vdc.
1.1.2 Range: -42Vdc to -60Vdc.
1.2 Environmental Ratings
1.2.1 Operating Ambient Temperature Range: 0°C to +40°C (+32°F to +104°F).
1.2.2 Storage Ambient Temperature Range: -40°C to +80°C (-40°F to +176°F).
1.2.3 Humidity: This system is capable of operating in an ambient relative humidity range of 0% to
95%, non-condensing.
1.2.4 Altitude: The maximum operating ambient temperature should be de-rated by 10°C at an
elevation of 10,000 feet above sea level. For elevations between 3,000 feet and 10,000 feet,
derate the maximum operating ambient temperature linearly.
1.2.5 Mounting: This product is intended only for installation in a Restricted Access Location on or
above a non-combustible surface.
Typical industry standards recommend minimum aisle space clearance of 2'6" for the front of
the relay rack and 2' for the rear of the relay rack.
This BDF/CBB uses natural convection. Equipment designed for use in environmentally
controlled space.
This product is intended for installation in Network Telecommunication Facilities (CO, vault,
hut, or other environmentally controlled electronic equipment enclosure).
This product is intended to be connected to the common bonding network in a Network
Telecommunication Facility (CO, vault, hut, or other environmentally controlled electronic
equipment enclosure).
1.3 Compliance Information
1.3.1 Safety Compliance: This BDF/CBB is UL Listed (and "cULus") as a DC Power Distribution
Center for Communications Equipment.
1.3.2 NEBS Compliance: Compliance verified by a Nationally Recognized Testing Laboratory
(NRTL) per GR-1089-CORE and GR-63-CORE. Contact Emerson Network Power for NEBS
compliance reports.
1.4 Output Ratings
1.4.1 Distribution Panel: 640A maximum continuous.
1.4.2 8-Panel Bay: 2400A, maximum, per side.
4800A, maximum, per bay.
1.4.3 6-Panel Bay: 1800A, maximum, per side.
3600A, maximum, per bay.
1.5 Standard Features—Lists 105 and 107
1.5.1 Fuse/Circuit Breaker Mounting Positions: See description in Distribution Panel List Options
section.
1.5.2 External Alarm Circuits: Three (3) Form-C relay contacts provided for external fuse / circuit
breaker alarms.
1.5.3 Local Controls and Indicators: A digital meter is furnished for load voltage and distribution
panel current monitoring. Each distribution panel has a green indicator which illuminates when
power is being supplied to the panel, and a red indicator which illuminates if a fuse or circuit
breaker within the panel opens.
1.5.4 Meter Accuracy
(A) Current: ±1A
(B) Voltage: ±0.5V