Application Guide
System Application Guide SAG582120600
Spec. No. 582120600 (Model 801DB
NVGB) Issue BF, February 21, 2014
Page 63 of 72
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Detail D (Page 3)
Optional List 117 Internal
Ground/Return Busbar
(List 127 similar)
Top Feed
DC Input Connections
(Battery Return Leads)
3/8" clearance holes on 1.00" centers
for installation of customer
provided two hole lugs.
(Torque to 180 in-lbs)
(Maximum Lug Width is 2.00")
(Maximum Wire Size is 4/0 AWG)
Top Feed
Installations
Bottom Feed
DC Input Connections
(Battery Return Leads)
3/8" clearance holes on 1.00" centers
for installation of customer
provided two hole lugs.
(Torque to 180 in-lbs)
(Maximum Lug Width is 2.00")
(Maximum Wire Size is 4/0 AWG)
Bottom Feed
Installations
Portion of bay removed
in illustration for clarity.
Rear View
8-Panel Bay
(6-Panel Bay Similar)
Home