Application Guide
System Application Guide SAG582120600
Spec. No. 582120600 (Model 801DB
NVGB) Issue BF, February 21, 2014
Page 61 of 72
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
DC Input Connections
3/8” clearance holes/slots on 1.00” centers
for installation of customer-
provided two hole lugs.
(Torque to 180 in-lbs)
(Maximum Lug Width is 2.00”)
(Maximum Wire Size is 750 kcmil)
Bottom Feed Installations
List 143, 144, 145 or 147
Input Feed and
Shunt Assembly
Addtional Input Feed and Shunt Assemblies
are installed on any Distribution Panel not
paralleled with a Distribution Panel that has
an Input Feed and Shunt Assembly installed.
List 143, 144, 145 or 147
Input Feed and
Shunt Assembly
3/8” clearance holes/slots on 1.00” centers
for installation of customer-
provided two hole lugs.
(Torque to 180 in-lbs)
(Maximum Lug Width is 2.00”)
(Maximum Wire Size is 750 kcmil)
Top Feed
Installations
List 143 or 147
List 143 or 147
Rear View
8-Panel Bay
(6-Panel Bay Similar)
Portion of bay removed
in illustration for clarity.
Home