Application Guide

System Application Guide SAG582120600
Spec. No. 582120600 (Model 801DB
NVGB) Issue BF, February 21, 2014
Page 53 of 72
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Fo
r in
ternal vo
lta
ge s
ensing,
set Se
nse
Opt
ion jump
er t
o In
ter
nal Sense
pos
iti
on.
F
or sy
ste
m ins
tallation w
ith
ext
ern
al ground/return bar, connect Return (+) sense leads from ground
bars to TB5-1 (Return B) and TB5-2 (Return A), and set Sense Option jumper to Extenal Sense position.
For optional external (ABS) power to the Meter/Alarm assembly, connect source A to TB1
and source B to TB2. Observe correct polarity as shown.
Connect Return (+) leads for Fused Auxiliary Loa
ds to system ground bar.
NOTES:
1.
2.
3.
F1
F2
F3
F4
F5
F6
Auxiliary Fuse Card
Located Behind
Removable Panel
External Sense
Internal Sense
Sense Option Jumper
(P/N 144134)
See Note 1
-48V
RTN
-48V
RTN
A B
1A (-48V)
2A (-48V)
3B (-48V)
4B (-48V)
Fused Aux.
Loads
See Note 3
ABS_A ABS_B
EXT
SNS
See
Note
1
TB5 TB1 TB2 TB3 TB4
See Note 2
2 1 2 1 2 1 2 1 2 1
Fuse Function
F1 Aux Load 1A
F2 Aux Load 2A
F3 Aux Load 3B
F4 Aux Load 4B
F5 ABS Power A
F6 ABS Power B
All fuses 1-1/3A.
External Sense, ABS and
Aux. Supply Connections
Home