Application Guide

SAG582120600 System Application Guide
Issue BF, February 21, 2014 Spec. No. 582120600 (Model 801DB
NVGB)
Page 52 of 72
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
TB9 TB7 TB8
NO C NC NO
C NCNO C
NCNO
C NC
For
Future Use
J3
J2
Network
(Factory
Connection)
Ethernet
Port
Input/Output Card Located behind Removable Panel
1 6 1 6 1 6
NO=Normally Open. C=Common. NC=Normally Closed.
All alarm relays are shown in de-energized state.
All relays
are de-energized for an alarm condition.
NOTE:
1.
Default Relay Mapping: K1 - Fuse Alarm
K
2 - Low Voltage Alarm
K3 - Power Lost Alarm
K4 - Overcurrent 1 Alarm, Overcurrent 2 Alarm
2.
Default Alarm Settings: Low Voltage Alarm - 51.8 VDC
Power Lost - 42.0 VDC
Overcurrent 1 - 480 amps
Overcurrent 2 - 800 amps
3.
K1 K2
K3 K4
External Alarms
See Note 1, 2
Detail B (Page 3)
List 106 and 108 (shown)
Ethernet and External
Alarm Connections