Lugs for Use with Lists 115 and 125 Distribution Panels
(two hole, 1/4” bolt clearance hole on 5/8” centers)
Lead Size (AWG) P/N
8 245390200
6 245346700
4 245346800
2 245346900
1/0 245393500 (special lug)
2/0 245393600 (special lug)
3/0 245393700 (special lug)
4/0 245393800 (special lug)
250 kcmil 514872 (special lug)
350 kcmil 514873 (special lug)
3-Pole Device Special Adapter 545346
Lugs for Use with P/Ns 547991, 556377, and 556378 Lug Adapter Kits
(two hole, 3/8” bolt clearance holes on 1” centers)
Wire Size
Part Number
6 AWG 245349900
4 AWG 245350000
2 AWG 245348200
1/0 AWG 245347100
2/0 AWG 245347200
3/0 AWG 245347300
4/0 AWG 245347400
250 kcmil 245347500
300 kcmil 245347600
350 kcmil 245347700
400 kcmil 245347800
500 kcmil 245347900
600 kcmil 245348000
750 kcmil 245348100
For one-pole circuit breaker, cables larger than 2 AWG require an H-TAP connection.
For two-pole circuit breaker, use special lugs per table.
For three-pole circuit breaker and 3-pole ground/return, use either special lugs per
table with adapter P/N 545346, or adapter kit P/N 547991, 556377, or 556378 with
2-hole lugs having 3/8” clearance holes on 1” centers.
For fuseblock (P/N 117201), cables larger than 2 AWG require H-tap. Special lugs
listed above can be used but will use two positions of the distribution panel.