TPL Fuses and Fuseblock
for Use in Lists 110 and 120
Ampere
Rating
Required
Distribution
Bus
Mounting
Positions
P/N
Lugs for Fuseblock
P/N 516241
70
2
248251500
See Table 4
80 2 248252000
100
2
248252600
150
2
248253300
200 2 248254000
225
2
248254500
250
2
248255000
Each fuse requires (1) Fuseblock P/N 516241.
See “Ordering Notes” in this section.
Fuseblock P/N 516241 also includes...
(1) P/N 248610301 alarm fuse (GMT-18/100A), and
(1) P/N 248898700 safety fuse cover (GMT-X).
See Table 9 for recommended load distribution wire sizes.
Table 3
TPL Fuses and Fuseblock
for Use in Lists 110 and 120 Distribution Panels
Lugs for Use with Fuseblock P/N 516241
Used in Lists 110 and 120 Distribution Panels
(single hole, 5/16” bolt clearance hole)
Lead Size (AWG) P/N
6 245351380
4
245351390
2
245351400
1 120224
Note: Cables larger than 2/0 AWG require an H-TAP connection.