Application Guide

System Application Guide SAG582120600
Spec. No. 582120600 (Model 801DB
NVGB) Issue BF, February 21, 2014
Page 19 of 72
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
List 145: Bay Input Feed and Shunt Assembly (2 Cables, 50 mV. Shunts)
Features
Provides landing points for two (2) input leads (on each side).
Provides an 800A, 50mV shunt (both sides).
Can be rotated for top or bottom feed configurations.
See DC Input Connections under Wiring Illustrations in ACCESSORY
DESCRIPTIONS for input termination specifications.
Restrictions
For use in Lists 105 and 107 only.
Ordering Notes
1) Order as required. Each List 145 provides input terminations and shunts for
both sides.
For top and bottom feed 2-load applications, order one (1) List 145 and specify
top or bottom feed.
For top and bottom feed multi-load applications, order one (1) List 145 for each
Side A/Side B load and specify top or bottom feed.
2) Order input lugs as required per DC Input Cable Sizes and Lugs Selection
under Wiring Notes in ACCESSORY DESCRIPTIONS.
List 147: Bay Input Feed and Shunt Assembly (4 Cables, 50 mV. Shunts)
Provides landing points for four (4) input leads (on each side).
Provides an 800A, 50mV shunt (one per side).
Can be rotated for top or bottom feed configurations.
See DC Input Connections under Wiring Illustrations in ACCESSORY
DESCRIPTIONS for input termination specifications.
Restrictions
For use in Lists 105 and 107 only.
Ordering Notes
1) Order as required. Each List 147 provides input terminations and shunts for
both sides.
For top and bottom feed 2-load applications, order one (1) List 147 and specify
top or bottom feed.
For top and bottom feed multi-load applications, order one (1) List 147 for each
Side A/Side B load and specify top or bottom feed.
2) Order input lugs as required per DC Input Cable Sizes and Lugs Selection
under Wiring Notes in ACCESSORY DESCRIPTIONS.
Home