15) Order bay frame grounding lugs as required per Bay Frame Grounding Wire Sizes and Lugs
Selection under Wiring Notes in ACCESSORY DESCRIPTIONS.
16) For remote access capability, order one (1) List 170 Ethernet option.
List 110: Distribution Panel, 8-Panel Bay
Features
♦ Twelve (12) TLS/TPS fuse positions, or six (6) TPL fuse positions, or a
combination of TLS/TPS and TPL fuse positions.
♦ Includes (12) TLS/TPS Fuseholders P/N 248817100. For panels factory
configured in a bay, each TPL Fuseholder P/N 516241 ordered replaces (2)
P/N 248817100 Fuseholders.
♦ See Load Distribution Connections under Wiring Illustrations in ACCESSORY
DESCRIPTIONS for load termination specifications.
Restrictions
640A maximum continuous.
For use in List 105 or List 108 only.
Ordering Notes
1) Order as required.
2) Specify up to twelve (12) TLS/TPS fuseholders, or up to six (6) TPL fuseholders, or a combination per
Distribution Panel (all positions MUST be filled). This instructs the factory how to configure the
Distribution Panel. Also specify mounting location for each configured Distribution Panel per bay. This
instructs the factory where to mount each configured Distribution Panel per bay.
3) Order distribution fuses and load lugs as required per Distribution Devices and Lug Selection in
ACCESSORY DESCRIPTIONS.
4) Replacement panels will be equipped with 12 TLS/TPS Fuseholders. TPL fuseholders (P/N 516241) may
be ordered to field modify the distribution panel. One TPL fuseholder takes the space of two TLS/TPS
fuseholders.
List 115: Distribution Panel, 8-Panel Bay
Features
♦ Sixteen (16) bullet nose circuit breaker and/or TLS/TPS Fuse (with bullet
nose fuseholder) positions.
♦ See Load Distribution Connections under Wiring Illustrations in
ACCESSORY DESCRIPTIONS for load termination specifications.
Restrictions
640A maximum continuous.
For use in List 105 or List 108 only.
Caution: Circuit breaker with a 150 ampere or greater rating SHALL HAVE
an empty mounting position between it and any other overcurrent
protective device.
Ordering Notes
1) Order as required.
2) Specify mounting location for each Distribution Panel per bay. This instructs the factory where to mount
each Distribution Panel when the bay is populated with different types of Distribution Panels.
3) Order distribution fuses, fuseholders, circuit breakers, and load lugs as required per Distribution Devices
and Lug Selection in ACCESSORY DESCRIPTIONS.
4) Order TVSS Device(s) as required per Transient Voltage Surge Suppressor (TVSS) Device in
ACCESSORY DESCRIPTIONS.