Application Guide

SAG582120600 System Application Guide
Issue BF, February 21, 2014 Spec. No. 582120600 (Model 801DB
NVGB)
Page 12 of 72
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
List 108: Common Equipment, 8-Panel Bay, w/ Advanced Metering
Features
List 108 provides the common equipment for an 8-Distribution Panel BDF/CBB (Battery Distribution
Fuse/Circuit Breaker Bay) with advanced metering.
Configurable for top or bottom feed.
Consists of a 7’H x 26”W x 15”D welded box framework (seismic, zone 4 earthquake compliant).
Includes an Advanced Meter/Alarm Panel that provides the following functions for each panel in the bay:
voltage and current metering and Low Voltage, Power Lost, Overcurrent, and Fuse/Circuit Breaker
alarms. Also provided are four (4) external alarm relay circuits, to which any combination of alarms can
be mapped.
Provides four (4) fused auxiliary -48V power outputs (1-1/3A), fused remote (A/B) meter panel inputs,
internal/external sense option, and an Ethernet connection (requires List 170 Ethernet option).
Restrictions
None.
Ordering Notes
1) Order up to eight (8) Lists 110 and/or List 115 Distribution Panels per bay.
2) If List 110 is ordered, order a List 150 Capacitor Precharge Assembly, if required.
3) For any open Distribution Panel position, order a List 118 Blank Panel.
4) Order List 143 or 144 Input Feed and Shunt Assembly as required. See Restrictions above. Each List
143 or 144 provides input terminations and shunts for both sides.
For top and bottom feed 2-load applications, order one (1) List 143 or 144 and specify top or bottom feed.
For top and bottom feed multi-load applications, order two (2) or four (4) List 143 or 144 for each Side
A/Side B load and specify top or bottom feed. Order List 130 as required.
List 110 Only: For 4-load side by side applications, order four (4) List 143 or 144, and order four (4)
556103. For top and bottom feed 2-load side by side applications, order two (2) List 143 or 144, two (2)
556103, and two (2) List 130.
List 115 Only: For 4-load side by side applications, order four (4) List 143 or 144, and order four (4)
557256. For top and bottom feed 2-load side by side applications, order two (2) List 143 or 144, two (2)
557256, and two (2) List 130.
5) If Distribution Panels (per side) are to be paralleled, order a List 130 Distribution Panel Paralleling Bar.
Each List 130 includes two (2) Paralleling Bars (one per side).
6) Order List 116 or List 117 Internal Ground Bars as required, or External Ground Bars (see ACCESSORY
DESCRIPTIONS section) as required.
7) List 116 provides input lug landing points at the top or bottom (as specified) of the full bay length
ground/return busbars. List 116 internal return bars are rated for 1200 Amps. List 148 is available to
increase that capacity to 2400 Amps and provide additional cable landing points. Each bay can
accommodate (1) List 148. List 148 offers cable termination at the rear of the bay and the option of a
bonding strap.
8) Order List 151 Cable Dressing Bars as required.
9) Order List 156 Meter and Alarm Card Input Power In-Line Fuse Kit as required.
10) Order a 1’, 2’, or 4-1/2’ Box Framework Extension as required.
11) Order distribution fuses, circuit breakers, and load lugs as required per Distribution Devices and Lug
Selection in ACCESSORY DESCRIPTIONS.
12) For Load and Load Return lug-mounting hardware, order Load Lug Hardware Kits (ship-loose) as
required, or order List 167 (pre-installed).
13) Order TVSS Device(s) as required per Transient Voltage Surge Suppressor (TVSS) Device in
ACCESSORY DESCRIPTIONS.
14) Order DC input lugs as required per DC Input Cable Sizes and Lugs Selection under Wiring Notes in
ACCESSORY DESCRIPTIONS.