Application Guide

System Application Guide SAG582140001
Spec. No. 582140001 (Model 801
NLDB, 801NLEB, 801NL-B) Issue AN, June 4, 2014
Page 91 of 115
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
5.2 AC Input Ratings
5.2.1 Voltage: Nominal 380/480 volts AC, three phase, 50/60 Hz, with an operating range of 260 to
530 volts. Acceptable input frequency range is 45 to 65 Hz.
Maximum non-destructive input voltage when rectifier is not operating: 600 VAC
5.2.2 Current: <13A @ 5800 W, and at an input voltage of 260 VAC.
5.2.3 THD (Total Harmonic Distortion): ≤5% when loaded at 50 to 100% of the rated output power.
5.2.4 Inrush Current: <150% of the rated input steady-state peak value.
5.2.5 Typical Input Data: 60 Hz input.
(A) System output is initially adjusted to 54.48 volts DC as measured at the system sense points
at 50% of full load and nominal input.
Number
of Rectifier
Modules
Installed
Nominal
Input
Voltage
Percent
of Full
Load
Input
Current
(Amperes)
Input
VA
Input
Watts
Power
Factor
Efficiency
%
Heat
Dissipation
BTU/Hr
1
408
0
0.488
343.8
52.54
0.156
-
179
25
2.4017
1693.46
1595.19
0.942
94.62
293
50
4.0168
2832.47
2795.47
0.986
96.18
365
75 6.1416 4328.16 4302.15 0.934 96.24 552
100 8.1106 5711.54 5693.69 0.996 95.89
798
110
8.4813
5972.18
5950.27
0.996
95.59
894
8.5230
6000.76
5979.37
0.996
95.37
944
480
0 0.568 471.83 52.34 0.111 - 179
25 2.0902 1735.52 1599.11 0.921 94.59 295
50
3.4514
2865.13
2789.56
0.974
96.21
361
75
5.2315
4342.83
4292.57
0.988
96.39
529
100 6.9714 5780.32 5742.72 0.993 96.15 754
110 7.2089 5974.45 5932.20 0.993 95.99 812
7.2456
6005.29
5961.03
0.992
95.70
874
(B) Typical Power Factor: Greater than or equal to 0.973 for any load greater than or equal to
50% of rated full load at nominal line. Meets IEC 1000-3-2.
(C) Typical Operating Efficiency: 96.39% at best point, 75% at full load and nominal input
voltage.
(D) Maximum Input Current: 8.597A at 100% of full load with output adjusted to 58 volts DC
as measured at the shelf output terminals, and input voltage as shown.
5.3 Environmental Ratings
5.3.1 Operating Ambient Temperature Range: -40°C to +65°C (-40°F to +149°F)
(A) Full rated output power of 5800 W for temperatures -40°C to +45°C (-40°F to +113°F).
(B) Power limitation for temperatures higher than +45°C (+113°F).
5.3.2 Storage Ambient Temperature Range: -40°C to +80°C (-40°F to +176°F).
5.3.3 Humidity: This system is capable of operating in an ambient relative humidity range of 0% to
95%, noncondensing.
5.3.4 Altitude: 2000 m (6560 ft) at full power (power limited for heights above 2000 m).
5.3.5 Acoustic Noise: 50dB(A), measured at a distance of 0.6 m from the rectifier.