Application Guide
System Application Guide SAG582140001
Spec. No. 582140001 (Model 801
NLDB, 801NLEB, 801NL-B) Issue AN, June 4, 2014
Page 81 of 115
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
4.2 AC Input Ratings
4.2.1 Voltage: Nominal 208 volts AC, three phase, 50/60 Hz, with an operating range of 176 to 264
volts. Acceptable input frequency range is 45 to 65 Hz.
Maximum non-destructive input voltage when rectifier is not operating: 600 VAC
4.2.2 Current: <18A @ 5800 W, and at an input voltage of 176 VAC.
4.2.3 THD (Total Harmonic Distortion): ≤5% when loaded at 50 to 100% of the rated output power.
4.2.4 Inrush Current: <150% of the rated input steady-state peak value.
4.2.5 Typical Input Data: 60 Hz input.
(A) System output is initially adjusted to 54.48 volts DC as measured at the system sense points
at 50% of full load and nominal input.
Number
of Rectifier
Modules
Installed
Nominal
Input
Voltage
Percent
of Full
Load
Input
Current
(Amperes)
Input
VA
Input
Watts
Power
Factor
%
Efficiency
%
Power
Loss
Watts
1
176
0
0.4135
128.32
111.48
76.9
0.78
110.6
25 5.139 1579.5 1522.7 96.9 89.12 165.62
50 9.571 2929 2922 99.7 92.03 232.82
75
14.476
4408
4405
99.9
91.43
377.6
100
19.651
5957
5950
99.8
91.04
509.4
110 21.68 6562 6552 99.8 90.09 578.4
120 21.89 6620 6608 99.8 89.17 638.1
208
0
0.3972
142.76
110.25
78.4
0.79
109.4
25
4.333
1570
1526
97.2
88.93
168.97
50 8.114 2930 2903 99.2 92.62 214.34
75
12.142
4371
4365
99.8
91.80
357.7
100
16.38
5873
5870
99.9
91.32
509.4
110 18.127 6489 6487 99.9 91.08 578.4
120 18.283 6545 6542 99.9 90.02 638.1
(B) Typical Power Factor: Greater than or equal to 99.2% for any load greater than or equal to
50% of rated full load at nominal line. Meets IEC 1000-3-2.
(C) Typical Operating Efficiency: 92.62% at best point, 90.25% at full load and nominal input
voltage.
(D) Maximum Input Current: 21.92A at 100% of full load with output adjusted to 58 volts DC
as measured at the shelf output terminals, and input voltage as shown.
4.3 Environmental Ratings
4.3.1 Operating Ambient Temperature Range: -40°C to +65°C (-40°F to +149°F)
(A) Full rated output power of 5800 W for temperatures -40°C to +45°C (-40°F to +113°F).
(B) Power limitation for temperatures higher than +45°C (+113°F).
4.3.2 Storage Ambient Temperature Range: -40°C to +80°C (-40°F to +176°F).
4.3.3 Humidity: This system is capable of operating in an ambient relative humidity range of 0% to
95%, noncondensing.
4.3.4 Altitude: 2000 m (6560 ft) at full power (power limited for heights above 2000 m).
4.3.5 Acoustic Noise: ≤50dB(A), measured at a distance of 0.6 m from the rectifier.