Between the AC input and the DC output: 20x10
6
Between the DC output and the enclosure: 20x10
6
(B) Dielectric Strength
Between the AC input and the enclosure: the leakage current is <1 mA, with no
breakdown within 1 minute using an applied voltage of 2120 V.
Between the AC input and the DC output: the leakage current is <1 mA, with no
breakdown within 1 minute using an applied voltage of 4242 V.
Between the DC output and the enclosure: the leakage current is <1 mA, with no
breakdown within 1 minute using an applied voltage of 707 V.
Between the DC output and the ground: the leakage current is <1 mA, with no
breakdown within 1 minute using an applied voltage of 1500 V (with the varistor and filter
capacitors removed before doing the test).
3.3.7 Surge Protection: Complies with IEEE C62 41-1991 Class B3, 6kV/3kA (1.2/50 µs surge
voltage and 8/20 µs surge current).
3.3.8 Compliance Information
(A) Safety and EMC: The rectifier has been recognized to meet the UL/EN/IEC 60950-2000
safety standard and is CE marked. The rectifier also meets the latest EMC requirements, as
listed in the following table.