Application Guide
System Application Guide SAG582140001
Spec. No. 582140001 (Model 801
NLDB, 801NLEB, 801NL-B) Issue AN, June 4, 2014
Page 71 of 115
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
3.2 AC Input Ratings
3.2.1 Voltage: Nominal 380/480 volts AC, three phase, 50/60 Hz, with an operating range of 260 to
530 volts. Acceptable input frequency range is 45 to 65 Hz.
Maximum non-destructive input voltage when rectifier is not operating: 600 VAC
3.2.2 Current: <13A @ 5800 W, and at an input voltage of 260 VAC.
3.2.3 THD (Total Harmonic Distortion): ≤5% when loaded at 50 to 100% of the rated output power.
3.2.4 Inrush Current: <150% of the rated input steady-state peak value.
3.2.5 Typical Input Data: 60 Hz input.
(A) System output is initially adjusted to 54.48 volts DC as measured at the system sense points
at 50% of full load and nominal input.
Number
of Rectifier
Modules
Installed
Nominal
Input
Voltage
Percent
of Full
Load
Input
Current
(Amperes)
Input
VA
Input
Watts
Power
Factor
%
Efficiency
%
Power
Loss
Watts
1
408
0
0.50
356
101
28.4
--
101.2
25 2.23 1576 1494 94.8 89.6 155.5
50 4.15 2930 2883 98.3 92.8 208.0
75
6.14
4337
4317
99.5
92.9
307.4
100
8.18
5783
5771
99.8
92.7
423.5
110 9.01 6368 6359 99.8 92.4 483.0
480
0 0.56 481 98 20.3 -- 97.8
25
1.95
1619
1487
91.8
90.0
148.0
50
3.54
2944
2876
97.8
93.0
201.0
75 5.22 4338 4313 99.4 93.0 299.8
100
6.95
5776
5757
99.6
92.9
409.7
110
7.64
6354
6341
99.8
92.7
465.5
(B) Typical Power Factor: Greater than or equal to 98% for any load greater than or equal to
50% of rated full load at nominal line. Meets IEC 1000-3-2.
(C) Typical Operating Efficiency: 93% at best point, 91% at full load and nominal input
voltage.
(D) Maximum Input Current: 9.1A at 100% of full load with output adjusted to 58 volts DC as
measured at the shelf output terminals, and input voltage as shown.
3.3 Environmental Ratings
3.3.1 Operating Ambient Temperature Range: -40°C to +65°C (-40°F to +149°F)
(A) Full rated output power of 5800 W for temperatures -40°C to +45°C (-40°F to +113°F).
(B) Power limitation for temperatures higher than +45°C (+113°F).
3.3.2 Storage Ambient Temperature Range: -40°C to +80°C (-40°F to +176°F).
3.3.3 Humidity: This system is capable of operating in an ambient relative humidity range of 0% to
95%, noncondensing.
3.3.4 Altitude: 2000 m (6560 ft) at full power (power limited for heights above 2000 m).
3.3.5 Acoustic Noise: ≤50dB(A), measured at a distance of 0.6 m from the rectifier.
3.3.6 Insulation Resistance and Dielectric Strength
(A) Insulation Resistance
• Between the AC input and the enclosure: ≥20x10
6
Ω