Application Guide

System Application Guide SAG582140001
Spec. No. 582140001 (Model 801
NLDB, 801NLEB, 801NL-B) Issue AN, June 4, 2014
Page 63 of 115
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Optional Battery Charge Temperature
Compensation Probe for Digital Compensation
Features
This system can be used with a Battery Charge Temperature Compensation Probe. This probe must be
mounted near the battery to sense battery ambient temperature. The probe connects to and allows the
MCA to automatically increase or decrease the output voltage of the system to maintain battery float
current as battery ambient temperature decreases or increases, respectively. Battery life can be
extended when an optimum charge voltage to the battery with respect to temperature is maintained.
Refer to the "Specifications" section of this document for further information.
Temperature Curve: The following figure details a user defined, via the MCA, Temperature
Compensation Probe Curve.
Ordering Notes
1) Order one Battery Charge Temperature Compensation Probe per power system. Part No. 107021 has a
25-foot long cord. Part No. 106824 has a 100 foot-long cord.
Typical Float Charge Thermal Characteristics
Using Optional Battery Charge Digital Temperature Compensation Probe
SLOPE
Adjustable from 0.0 V / °C
to 0.2 V / °C
MIN W/T
Adjustable from
Float to 44V
MAX W/T
Adjustable from
Float to 58.5V max.*
+25°C
(+77°F)
FLOAT
Determines Float Mode
Output Voltage at 25°C.
Adjustable from 47.0V
to 58.0V max.*
Temperature
IncreasingDecreasing
Voltage
Decreasing
Increasing
* Maximum setting is automatically
limited to 1.0 volt less than HVSD setting.