AC Input (6 AC Input Feeds)
Wire and Conduit Sizes, Branch Circuit Protection, and Lugs Selection
Lists 6 and 14
Features
10-32 studs on 5/8” centers are provided for installation of customer provided two-hole AC Input lugs.
1/4-20 studs are provided for installation of customer provided two-hole AC equipment grounding lugs.
For AC input wiring, refer to the illustration provided in this section.
Restrictions
Six (6) AC input feeds are required in Lists 6 and 14 only.
6 Feeds, 480V, List A w/ List 6 or 14: One feed per conduit and one ground per conduit. Customer must
provide a 40-50A high inrush circuit breaker overcurrent protection device in each AC input feed.
All lugs for equipment grounding connections must be ordered separately. Customer needs to supply lug
mounting hardware.
Ordering Notes
1) Refer to Table 15 for recommended AC input wire and conduit sizes, branch circuit protection, and
equipment grounding lugs.