Application Guide
System Application Guide SAG582140001
Spec. No. 582140001 (Model 801
NLDB, 801NLEB, 801NL-B) Issue AN, June 4, 2014
Page 51 of 115
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
24 Feeds
Input
Voltage
Input
Current
Overcurrent
Protection
(1)
40°C Ambient
Temperature
(2)
Wire
AWG
(2)
(3)
Conduit
Size (in.)
THWN - 75°C Wire - Individual Feed
Three Rectifiers (9 Current and 1 Ground Wire) per Conduit
480V 7.8A 15A 14 1/2
380V 10A 15A 14 1/2
208V
18A
25A
10
3/4
THHN - 90°C Wire - Individual Feed
Three Rectifiers (9 Current and 1 Ground Wire) per Conduit
480V 7.8A 15A 14 1/2
380V 10A 15A 14 1/2
208V 18A 25A 10 3/4
Recommended Equipment Grounding Wire Crimp Lugs
Wire AWG Crimp Lug P/N
(4)
14 245359650
10 245342300
8 245346600
1
The AC input branch circuit protective device should be of the
time-delay or high inrush type.
2
Wire sizes based on recommendations of the American National
Standards Institute (ANSI) approved National Fire Protection
Association's (NFPA) National Electrical Code (NEC). Table
310-16 for copper wire at 75°C and 90°C conductor temperature;
operating in an ambient of 40
°C was used. For other operating
ambient temperatures, refer to the National Electrical Code. For
operation in countries where the NEC is not recognized, follow
applicable codes.
3
Equipment grounding conductors must be provided with the AC
input conductors supplied to the Bay. Frame ground terminals
must be connected to earth ground, not power system neutral.
Equipment grounding conductor size based on recommendations
of the NEC Table 250-122 for copper wire. When aluminum or
copper clad aluminum grounding conductor is used, refer to Table
250-122 for increased conductor size. For operation in countries
where the NEC is not recognized, follow applicable codes.
4
Single-hole lug, 1/4" bolt clearance hole.
Table 13
Recommended AC Input Wire and Conduit Size, and Lug Selection
(24 AC Input Feeds, 1 per Rectifier Module)