Application Guide

SAG582140001 System Application Guide
Issue AN, June 4, 2014 Spec. No. 582140001 (Model 801
NLDB, 801NLEB, 801NL-B)
Page 44 of 115
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Power Bay DC Output Cable Sizes and Lugs Selection
Features
3/8” clearance holes on 1" centers are provided for installation of customer provided DC output cables
terminated in two-hole lugs. These are accessed from the rear of each Power Bay.
For lug mounting hole size and spacing dimensions, refer to the illustration provided in this section.
Restrictions
All lugs for customer connections must be ordered separately.
Customer needs to supply lug mounting hardware.
Maximum size of wire to be connected to a single lug position is 750 kcmil (2 per lug position).
Maximum lug width, 1.937 inches.
Ordering Notes
1) DC output cable size varies depending on power requirements, therefore no specific information is
provided for cable size. Refer to Table 11 for recommended cable sizes and lugs at rated maximum bay
output (2400 amperes). When making connections, observe correct polarity.
2) For other available lugs and hardware, refer to drawings 031110100 through 031110300.
Ambient Operating
Temperature
(1)
Loop
Length
(2)
(Ft)
Recm 90
°
C
Wire Size
(1, 2)
Recommended
Crimp Lug
(3)
30°C
140
(5) 750 kcmil
245392000
40°C
140
(5) 750 kcmil
168
(6) 750 kcmil
1
Cable sizes are based on recommendations of the American National Standards Institute
(ANSI) approved National Fire Protection Association's (NFPA) National Electrical Code
(NEC). Table 310-16 for copper wire rated at 90
°C conductor temperature operating in
ambients of 30
°C and 40°C was used. For other operating ambient temperatures, refer to the
NEC. For operation in countries where the NEC is not recognized, follow applicable codes.
2
Recommended cable sizes are sufficient to restrict voltage drop to 1.0 volt or less at rated full
output current of the bay for the loop lengths shown. Loop length is the sum of the lengths of
the positive and negative leads.
3
Two-hole lug, 3/8" bolt clearance hole, 1" centers. Refer to drawing 031110100 for lug
crimping information.
Table 11
Recommended Power Bay DC Output Cable Size and Lug Selection