Application Guide

System Application Guide SAG582140001
Spec. No. 582140001 (Model 801
NLDB, 801NLEB, 801NL-B) Issue AN, June 4, 2014
Page 43 of 115
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Fuse/
Circuit
Breaker
Amperage
Recm 90
°
C Wire Size
(1)
2/0 AWG 3/0 AWG 4/0 AWG 250 kcmil 300 kcmil 350 kcmil 400 kcmil
Loop Length (feet)
(2)
300A
-- -- --
150
(3, 4)
(2) Wires
90
(3)
105
(3, 4)
120
(3, 4)
350A
68
(3, 4)
(2) Wires
86
(3, 4)
(2) Wires
108
(3, 4)
(2) Wires
128
(3, 4)
(2) Wires
-- 90
(3)
103
(3)
400A
75
(3, 4)
(2) Wires
95
(3, 4)
(2) Wires
112
(3, 4)
(2) Wires
-- -- --
450A
--
67
(3)
(2) Wires
84
(3, 4)
(2) Wires
100
(3, 4)
(2) Wires
120
(3, 4)
(2) Wires
-- --
500A
--
76
(3)
(2) Wires
90
(3, 4)
(2) Wires
108
(3, 4)
(2) Wires
126
(3, 4)
(2) Wires
--
600A
-- -- --
90
(3)
(2) Wires
135
(3, 4)
(3) Wires
105
(3, 4)
(2) Wires
120
(3, 4)
(2) Wires
800A
-- -- --
84
(3)
(3) Wires
101
(3, 4)
(3) Wires
118
(3, 4)
(3) Wires
135
(3, 4)
(3) Wires
Recommended Crimp Lug
(5)
Lug
245347200
(per cable)
245347300
(per cable)
245347400
(per cable)
245347500
(per cable)
245347600
(per cable)
245347700
(per cable)
245347800
(per cable)
1
Wire sizes based on recommendations of the American National Standards Institute (ANSI) approved
National Fire Protection Association's (NFPA) National Electrical Code (NEC). Table 310-16 for copper
wire at 90°C conductor temperature operating in ambients of 30
°C and 40°C was used. For other operating
ambient temperatures, refer to the National Electrical Code. For operation in countries where the NEC is
not recognized, follow applicable codes.
2
Recommended wire sizes are sufficient to restrict voltage drop to 1.0 volt or less at listed branch current for
the loop lengths shown. Loop length is the sum of the lengths of the positive and negative leads.
3
Wire Size / Loop Length Combination Calculated using 30°C Ambient Operating Temperature.
4
Wire Size / Loop Length Combination Calculated using 40°C Ambient Operating Temperature.
5
Two-hole lug, 3/8" bolt clearance hole, 1" centers. Refer to drawing 031110100 for lug crimping
information.
Table 10 (cont'd from previous page)
Recommended Load Distribution Wire Size and Lug Selection for
TPL Fuse and 218 Circuit Breaker (Load Side)