Application Guide
SAG582140001 System Application Guide
Issue AN, June 4, 2014 Spec. No. 582140001 (Model 801
NLDB, 801NLEB, 801NL-B)
Page 42 of 115
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Fuse/
Circuit
Breaker
Amperage
Recm 90
°
C Wire Size
(1)
6
AWG
4
AWG
2
AWG
1/0
AWG
2/0
AWG
3/0
AWG
4/0
AWG
250
kcmil
300
kcmil
350
kcmil
Loop Length (feet)
(2)
70A
33
(3)
53
(3, 4)
85
(3, 4)
135
(3, 4)
-- -- -- -- -- --
80A
-- 47
(3, 4)
74
(3, 4)
118
(3, 4)
-- -- -- -- -- --
100A
-- -- 59
(3, 4)
95
(3, 4)
119
(3, 4)
-- -- -- -- --
125A
-- -- 47
(3)
76
(3, 4)
95
(3, 4)
120
(3, 4)
-- -- -- --
150A
-- -- -- 63
(3, 4)
79
(3, 4)
100
(3, 4)
-- -- -- --
175A
-- -- -- -- 68
(3, 4)
86
(3, 4)
108
(3, 4)
-- -- --
200A
-- -- -- -- -- 75
(3, 4)
95
(3, 4)
112
(3, 4)
-- --
225A
-- -- -- -- -- 67
(3)
84
(3, 4)
100
(3, 4)
120
(3, 4)
--
250A
-- -- -- -- -- -- 76
(3)
90
(3, 4)
108
(3, 4)
126
(3, 4)
Recommended Crimp Lug
(5)
Lug
2453-
49900
2453-
50000
2453-
48200
2453-
47100
2453-
47200
2453-
47300
2453-
47400
2453-
47500
2453-
47600
2453-
47700
1
Wire sizes based on recommendations of the American National Standards Institute (ANSI) approved
National Fire Protection Association's (NFPA) National Electrical Code (NEC). Table 310-16 for copper
wire at 90°C conductor temperature operating in ambients of 30
°C and 40°C was used. For other operating
ambient temperatures, refer to the National Electrical Code. For operation in countries where the NEC is
not recognized, follow applicable codes.
2
Recommended wire sizes are sufficient to restrict voltage drop to 1.0 volt or less at listed branch current for
the loop lengths shown. Loop length is the sum of the lengths of the positive and negative leads.
3
Wire Size / Loop Length Combination Calculated using 30°C Ambient Operating Temperature.
4
Wire Size / Loop Length Combination Calculated using 40°C Ambient Operating Temperature.
5
Two-hole lug, 3/8" bolt clearance hole, 1" centers. Refer to drawing 031110100 for lug crimping
information.
Table 10 (cont'd on next page)
Recommended Load Distribution Wire Size and Lug Selection for
TPL Fuse and 218 Circuit Breaker (Load Side)