Wiring Components
Load Distribution Wire Sizes and Lugs Selection (Distribution Bay)
Features
♦ Load distribution leads are connected as described in the section titled Distribution Devices under
"Accessory Descriptions".
♦ For lug mounting hole size and spacing dimensions, refer to the illustrations in the section titled
Distribution Devices under "Accessory Descriptions".
Restrictions
All lugs for customer connections must be ordered separately.
Ordering Notes
1) The type of distribution device determines the load lug hole size and spacing requirements. The rating of
the distribution device determines the wire size requirements. For wire size and lug selection; refer to
Table 9 and Table 10 (Load Side). (Load return leads are terminated outside the bay to customer
provided return busbars.)
2) For other available lugs and hardware, refer to drawings 031110100 through 031110300.