Ampere
Rating
No.
of
Poles
Required
Distribution Bus
Mounting
Positions
Circuit Breaker
Part Number
Lug Adapter Kit
Part Number
(Qty 1)
Electrical Trip
1
(White Handle)
Electrical/
Mechanical Trip
2
(Black Handle)
100 1 1 513766 513767 not required
125 1 1 513768 513769 not required
150 1 1 513770 513771 not required
175 1 1 513772 513773 not required
200
1
1
513774
513775
not required
225
1
1
513776
513777
not required
250
1
1
513778
513779
not required
300
2
2
513780
513781
529132
350
2
2
513782
513783
529132
400
2
2
513784
513785
529132
450
3
3
513786
513787
529131
500
3
3
513788
513789
529131
600
3
3
513790
513791
529131
800
4
4
513792
513793
534420
See Table 10 for recommended load distribution wire sizes and lugs.
Circuit Breaker Alarm Operation:
1
Provides an alarm during an electrical trip condition only.
2
Provides an alarm during an electrical or manual trip condition.
Table 1
218 Circuit Breaker Assemblies