List 0C: 24 Position Bullet-Nose Circuit Breaker/Fuse Panel
Features
Provides twenty-four (24) Bullet
Nose Device positions.
Accepts a choice of TLS/TPS-type
fuseholders, Bullet Nose-Type
circuit breakers, or Bullet Nose-
Type GMT Fuse Modules.
The List C Fuse/Circuit Breaker
Panel is equipped with one (1)
shunt for all distribution positions for
MCA load current measurements.
Refer also to Bullet Nose-Type
Circuit Breakers and Bullet Nose-
Type Fuseholders e/w TLS/TPS
Fuses and Optional Bullet Nose-
Type 10-Position GMT Fuse
Module for List C.
Restrictions
Each Distribution Bay can be equipped
with only one (1) List C panel.
The List C Circuit Breaker/Fuse Panel
requires distribution position #12 in the
Bus #1 Distribution Panel.
Current monitoring for the List C
Fuse/Circuit Breaker Panel is for the
complete panel. Circuit Breakers
and/or fuses are not individually
monitored.
When installed, the bay can be loaded with up to (47) 218 Circuit Breakers or (23) TPL Fuses and (24) Bullet
Nose Circuit Breakers or TLS/TPS Fuses.
The List C Circuit Breaker/Fuse Panel is rated for a maximum continuous load of 500 amps.
The total load combination of List C and Distribution Panel #1 cannot exceed 1500A.
Ordering Notes
1) Order as required.
2) Also order distribution fuses, circuit breakers, and/or Bullet Nose-Type 10-Position GMT Fuse Modules as