R48-5800 Rectifier Electrical Specifications*
AC Input
Nominal Voltage Three phase 380/480VAC
Operating Voltage Range R48-5800: 304VAC to 530VAC (output reduced 50% from 260-304VAC)
R48-5800L: 145VAC to 230VAC (output reduced 50% from 145-176VAC)
Frequency 45 Hz to 65 Hz
Power Factor (PF) >0.98 from 50% to 100% load
Total Harmonic Distortion <5% from 50% to 100% load
Input Current Max 20 amp
Inrush Current Inrush current does not exceed 150% of the rated input steady state peak value.
Input Protection If the input voltage decreases or increases beyond a non-adjustable predetermined value, the recti-
fier circuitry shuts down, disabling the output. The rectifier will recover automatically when the
AC input is re-established and exceeds 260VAC (low voltage restart point) or when it decreases to
530VAC (high voltage restart point). Overcurrent is protected by an internal fuse.
Operating Efficiency 93% peak
92.6% at full load
DC Output
Output Voltage Range -42.0VDC to -58.0VDC
Output Power 5800W maximum from 304VAC to 530VAC
Output Current Nominal 110 amps, adjustable from 10-110 amps
Regulation Steady state output voltage remains within +/-0.25% for any combination of input voltage
from 5% to 100% load
Voice Band Noise The voice-frequency noise generated by a rectifier does not exceed 32dBrnC output noise
from 10% to 100% load
Wide Band Noise Does not exceed 250 mv peak-to-peak, or 100 mv rms per Telcordia GR-947-CORE
Psophometric Noise Does not exceed 1 mv from 10% to 100% load
Protection
Current Limiting The output current is limited to 110 amps
Over Current Internal fuse
High Voltage Shutdown If rectifier detects over voltage it will turn off. After 5 seconds it will restart; if it encounters an over
voltage within 5 minutes it will turn off and remain off until reset.
Additional Information
For ordering information, request SAG582140001. For additional specification, engineering and installation
information use specification number 582140001, model number 801 NLEB.
Emerson Network Power —
a complete spectrum of best-in-class reliable
power, precision environmental and connectivity
solutions for today’s telecommunications and
data network infrastructure
120
100
80
60
40
20
0
250 300 350 400 450 500 550
Input Voltage (VAC)
% of max output power
Output Power vs. Input Voltage
at Ambient Temp. <45°C
120
100
80
60
40
20
0
-40 -20 -10 10-30 0 20 30 40 50 60 70 80
Temperature (C°)
% of max output power
Output Power vs. Temperature
at Input Voltage >304VAC
70
60
50
40
30
20
10
0
0 10 20 30 40 50 60 70 80 90 110100 160150120 130 140
Output Current (A)
Output Voltage (V)
Output Voltage vs. Output Current,
max. Output Power 5800W
*Specify R48-5800L for 208V.