84
Figure 9. Local Menu Flow Diagrams (cont’d from previous page, cont’d on next page)
ESC
B5
EN T
EIB
EIB 1
Shunt 1 Set
As
Not Used
(Not Used / General / Load / Battery)
Shunt 2 Set
As
Not Used
(Not Used / General / Load / Battery)
Shunt 3 SetAs
Not Used (Not Used / General / Load / Battery)
Shunt 1 Current
500.0
A (50.0-50000.0)
Shunt 1
Voltage
75.0 mV (1.0-150.0)
Shunt 2 Current
500.0
A
(50.0-50000.0)
Shunt 2
Voltage
75.0 mV (1.0-150.0)
Shunt 3 Current
500.0 A
(50.0-50000.0)
Shunt 3
Voltage
75.0 mV
(1.0-150.0)
Voltage
Type
48 (Block 4)
(disable / 24 (block 2) /
midpoint / 48 (block 4))
Blk V Dif
f(12V)
1
(0 - 2)
Blk V Di
ff(Mid)
1 (0 - 2)
Block In-Use
0 (0-8)
EIB 1
ESC
B7
EN T
SMTemp
SMTemp 1
T1 Assign Equip
Ambient (None / Battery /Ambient)
...
T8 Assign Equip
None (None / Battery /Ambient)
SM
Temp 1
ESC
B6
EN T
SMDU
SMDU 1
Shunt 1
Voltage
75 mV (25-75)
Shunt 1 Current
500 A
(100-2000)
Shunt 2 Voltage
75 mV (25-75)
Shunt 2 Current
500 A
(100-2000)
Shunt 3 Voltage
75 mV (25-75)
Shunt 3 Current
500 A
(100-2000)
Shunt 4 Voltage
75 mV (25-75)
Shunt 4 Current
500
A (100-2000)
Shunt 5 Voltage
75 mV
(25-75)
Shunt 5 Current
500
A (100-2000)
Shunt 1 SetAs
Not Used (Not Used / General / Load / Battery)
Shunt 2 SetAs
Not Used
(Not Used / General / Load / Battery)
Shunt 3 Set
As
Not Used
(Not Used / General / Load / Battery)
Shunt 4 Set
As
Not Used
(Not Used / General / Load / Battery)
Shunt 5 Set
As
Not Used (Not Used / General / Load / Battery)
SMDU 1
ESC
B4
EN T
ENT
L
VD
L
VD Group
LVD Unit
SMDU 1
LVD
HTD Recon Point
38.0 deg. C
(20-80)
HTD Point
40.0 deg. C
(20-80)
L
VD Group
ESC
L
VD1
Enable
(enable / disable)
LVD1 Mode
Voltage
(voltage / time)
L
VD1 V
olt
42.0 V
(40-60) (20-30)
L
VD1 Recon Volt
49.0 V
(40-60) (20-30)
LVD1 ReconDelay
1 min
(1-30)
LVD1 Time
300 min (30-1000)
LVD1 Dependency
None
(none / LVD1 / LVD2)
LVD2
Enable (enable / disable)
LVD2 Mode
Voltage
(voltage / time)
LVD2 V
olt
42.0 V
(40-60) (20-30)
LVD2 Recon Volt
49.0 V
(40-60) (20-30)
LVD2 ReconDelay
1 min (1-30)
LVD2
Time
600 min (30-1000)
LVD2 Dependency
None (none /
LVD1 / L
VD2)
HTD1
Disable
(enable / disable)
HTD2
Disable
(enabled / disable)
LVD T
ype
Bistable
(bistable / mono-stable / mono w/sample)
LVD Unit
LVD 1
Enable
(enable / disable)
LVD 1 Mode
V
oltage (voltage / time)
LVD 1
Voltage
42.0 V
(40-60) (20-30)
LVD1 Recon
Volt
49.0 V
(40-60) (20-30)
LVD1 ReconDelay
1 min
(1-30)
LVD 1
Time
300 min
(30-1000)
LVD1 Dependency
None (none /
LVD1 / LVD2)
LVD 2
Enable (enable / disable)
LVD 2 Mode
Voltage (voltage / time)
LVD 2 Voltage
42.0 V (40-60) (20-30)
LVD2 Recon Volt
49.0 V (40-60) (20-30)
L
VD2 ReconDelay
1 min (1-30)
LVD 2 Time
600 min (30-1000)
LVD2 Dependency
None (none / LVD1 / LVD2)
HTD 1
Disable (enable / disable)
HTD 2
Disable (enabled / disable)
SMDU 1 L
VD
EN
T
ESC
EN
T
ESC
Displayed when “
Voltage
Type”
set for other then “disable” and
“Block In-Use” set for other then “0”.