Brochures and Data Sheets

NetSure
ACU+ Controller (Advanced Control Unit Plus)
User Instructions, UM1M820BNA (Issue AK, March 3, 2014)
Spec. No: 1M820BNA, 1M820DNA Code: UM1M820BNA
Model No: M820B, M820D Issue AK, March 3, 2014
83
Figure 9. Local Menu Flow Diagrams (cont’d from previous page, cont’d on next page)
Battery
Basic
Charge
Test
Temp Comp
Capacity
Battery 1
Num Batt Shunts
1 (0-2)
Calc Batt Curr
No (no / yes)
Low Capacity Pt
75 % (25-100)
Current Limited
No (no / yes)
BTRM TempSensor
IB2 T2 (None / SMTemp8 T8 / ... / SMTemp8 T1 / ... /
SMTemp1 T8 / ... / SMTemp1 T1 / EIB T2 / EIB T1 /
IB2 T2 / IB2 T1 / System T3 / System T2 / System T1 /
Average SMBRC / Average / Maximum)
BTRM Temp High2
100.0 deg. C (0-100)
BTRM Temp High1
90.0 deg. C (0-100)
BTRM Action
Disabled (disabled / lower voltage)
BTRM Voltage
51.0 V (45-55) (22.5-27.5)
ABCL Point
20A (1-60)
Float Voltage
54.0 V (42.0-58.0) (21.0-29.0)
EQ Voltage
56.5 V (42.0-58.0) (21.0-29.0)
Batt Curr Limit
0.10 C10 (0.10-0.25)
Over Curr Lmt
0.30 C10 (0.30-1.00)
Auto EQ
No (no / yes)
EQ Start Curr
0.060 C10 (0.040-0.080)
EQ Start Cap
80.0 % (0-99)
EQ Stop Curr
0.010 C10 (0.002-0.020)
EQ Stop Delay
180 min (0-1440)
Maximum EQ Time
1080 min (60-2880)
Cyc EQ
No (no/yes)
Cyc EQ Interval
100 days (2-365)
Cyc EQ Duration
720 min (30-2880)
Test Volt Lmt
45.0 V (43.0-53.5) (21.5-27.0)
Test End Volt
45.2 V (43.2-53.5) (21.5-27.0)
End Test Time
100 min (10-1440)
EndTestCapacity
70 % (0-100)
RecordThreshold
0.100 V (0.100-1.000)
AC Fail Test
Disabled (disabled / enabled)
Planned Tests
0 (0-12)
Test 1 (M-D Hr)
10-21 10
Const Curr Test
Disabled (disabled / enabled)
ConstCurrT Curr
9999.0 A (1-9999)
Short Test
Disabled (disabled / enabled)
ShortTest Cycle
30 days (1-365)
Short Test Time
5 min (1-60)
Max Diff Curr
0
.05 C10 (0.00-1.00)
BattTestLowCap
99 % (70-100)
Temp CompCenter
25.0 deg. C (0.0-40.0)
Temp Comp Coeff
72.0 mV/deg. C (0.0-500.0)
TempComp Sensor
None (None / SMTemp8 T8 / ... / SMTemp8 T1 / ... /
SMTemp1 T8 / ... / SMTemp1 T1 / EIB T2 / EIB T1 /
IB2 T2 / IB2 T1 / System T3 / System T2 / System T1 /
Average SMBRC / Average / Maximum)
Comp Temp High2
60 deg. C (0-100)
Comp Temp High1
50 deg. C (0-100)
Comp Temp Low
-10.0 deg. C (-40 to +100)
Temp Comp Max V
29.0 (42.0-58.0) (21.0-29.0)
Temp Comp Clamp
Enabled (disabled / enabled)
Temp Comp Min V
2
6.0 (42.0-58.0) (21.0-29.0)
Charging Eff
96 % (10-100)
Time 0.1C10
10.00 h (0.00-10.00)
Time 0.2C10
4.90 h (0.00-10.00)
Time 0.3C10
3.00 h (0.00-10.00)
Time 0.4C10
2.00 h (0.00-10.00)
Time 0.5C10
1.40 h (0.00-10.00)
Time 0.6C10
1.20 h (0.00-10.00)
Time 0.7C10
1.10 h (0.00-10.00)
Time 0.8C10
0.90 h (0.00-10.00)
Time 0.9C10
0.70 h (0.00-10.00)
Time 1.0C10
0.50 h (0.00-10.00)
Rated Capacity
600.0 Ah (50.0-50000.0)
Shunt Current
800.0 A (50.0-50000.0)
Shunt Voltage
25.0 mv (1.0-150.0)
ENT
ENT
ENT
ENT
ENT
ESC
ESC
ESC
ESC
ESC
ESC
ENT
ESC
B3
ENT
Basic
Charge
Test
Temp Comp
Capacity
Battery 1
To Change a Parameter:
Press or to move up and
down list of parameters.
Press ENT to highlight selected parameter.
Press or to change highlighted value.
Press ENT to make the change.
Press ESC to cancel the change.
The parameter values shown in ( ) are the
adjustment range or acceptable values.
Factory default settings are listed in the
ACU+ Configuration Drawing (C-dwg)
furnished with your system.
To Select a Sub-Menu:
Press or to move cursor in
menu screen (selects menu item).
Press ENT to enter selected sub-menu.