Brochures and Data Sheets

NetSure
ACU+ Controller (Advanced Control Unit Plus)
User Instructions, UM1M820BNA (Issue AK, March 3, 2014)
Spec. No: 1M820BNA, 1M820DNA Code: UM1M820BNA
Model No: M820B, M820D Issue AK, March 3, 2014
51
Table 5
Full Alarm Name WEB
(Abbreviated
Alarm Name - LCD)
Alarm Description Action to Correct
OB Battery Fuse Alarms (SM-DU Module must be present in system)
(OB Batt Fuse)
Fuse 1 Alarm
(Fuse 1 Alarm)
Fuse #1 is open.
Find out and eliminate the reason the
fuse is open before replacing. Check
for overload or short circuit. If the fuse
was manually removed, check with
the person that removed it before
reinserting it.
Fuse 4 Alarm
(Fuse 4 Alarm)
Fuse #4 is open.
SMDU Battery Fuse Unit Alarms (SM-DU Module must be present in system)
(SMDU Bat Fuse)
Batt Fuse 1 Alarm
(Batt Fuse 1 Alm)
Battery fuse #1 is open.
Find out and eliminate the reason the
fuse is open before replacing. Check
for overload or short circuit. If the fuse
was manually removed, check with
the person that removed it before
reinserting it.
Batt Fuse 4 Alarm
(Batt Fuse 4 Alm)
Battery fuse #4 is open.
DC Distribution Alarms
(DC Distr)
Over Voltage 1
(Over Voltage 1)
DC output is above over voltage 1
threshold.
Check to see why voltage is high.
Over Voltage 2
(Over Voltage 2)
DC output is above over voltage 2
threshold.
Under Voltage 1
(Under Voltage 1)
DC output is below under voltage 1
threshold.
Check to see why voltage is low.
Under Voltage 2
(Under Voltage 2)
DC output is below under voltage 2
threshold.
Over Voltage 1 (24V)
(24V Over Volt1)
DC output is above over voltage 1
threshold.
Check to see why voltage is high.
Over Voltage 2 (24V)
(24V Over Volt2)
DC output is above over voltage 2
threshold.