50
Table 5
Full Alarm Name WEB
(Abbreviated
Alarm Name - LCD)
Alarm Description Action to Correct
High Switch DisTemp
(HiSwitchDisTemp)
Li-Ion battery has high switch
discharge temperature.
Check why temperature is high.
Charge Short Circuit
(Char ShortCirc)
Li-Ion battery has charge short circuit
condition.
Replace the battery.
DisChar Short Circuit
(DisCharShortCir)
Li-Ion battery has discharge short
circuit condition.
Replace the battery.
High Switch CharTemp
(HiSwitchCharTem)
Li-Ion battery has high switch charge
temperature.
Check why temperature is high.
Hardware Fail 20
(HardwareFail20)
Li-Ion battery has hardware failure. Replace the battery.
Hardware Fail 21
(HardwareFail21)
Li-Ion battery has hardware failure. Replace the battery.
High Charge Current
(Hi Charge Curr)
Li-Ion battery has high charge
current.
Check why charge current high.
High DisCharge Current
(Hi Dischar Curr)
Li-Ion battery has high discharge
current.
Check why discharge current high.
Communication Interrupt
(Comm Interrupt)
Li-Ion battery communications have
been interrupted.
Check why communications failure.
Battery Disconnected
(Batt Disconnect)
Li-Ion battery is disconnected. Check why battery disconnected.
Charge Enabled
(Charge Enable)
Li-Ion battery charge is enabled. --
Battery Discharging
(Batt Discharge)
Li-Ion battery is discharging. --
Battery Charging
(Batt Charge)
Li-Ion battery is charging. --
DisCharging
(DisCharging)
Li-Ion battery is discharging. --
Charging(5A)
(Charging(5A))
Li-Ion battery is charging. --
DisCharging(5A)
(DisCharging(5A))
Li-Ion battery is discharging. --
Battery Relay Status
(BattRelayStatus)
State of alarm relay. If in alarm state, check battery.