User Instructions, UM1M820BNA (Issue AK, March 3, 2014)
Spec. No: 1M820BNA, 1M820DNA Code: UM1M820BNA
Model No: M820B, M820D Issue AK, March 3, 2014
36
Table 5
Full Alarm Name WEB
(Abbreviated
Alarm Name - LCD)
Alarm Description Action to Correct
EIB Temp1 High 2
(EIB T1 Hi2)
Temperature sensor #1 (connected to
EIB board and set as Ambient)
sensing temperature higher than high
temperature threshold 2.
Check why temperature is high or
low.
EIB Temp1 High 1
(EIB T1 Hi1)
Temperature sensor #1 (connected to
EIB board and set as Ambient)
sensing temperature higher than high
temperature threshold 1.
EIB Temp1 Low
(EIB T1 Low)
Temperature sensor #1 (connected to
EIB board and set as Ambient)
sensing temperature lower than low
temperature threshold.
EIB Temp2 High 2
(EIB T2 Hi2)
Temperature sensor #2 (connected to
EIB board and set as Ambient)
sensing temperature higher than high
temperature threshold 2.
Check why temperature is high or
low.
EIB Temp2 High 1
(EIB T2 Hi1)
Temperature sensor #2 (connected to
EIB board and set as Ambient)
sensing temperature higher than high
temperature threshold 1.
EIB Temp2 Low
(EIB T2 Low)
Temperature sensor #2 (connected to
EIB board and set as Ambient)
sensing temperature lower than low
temperature threshold.
SMTemp1 Temp1 High 2
(SMTemp1 T1 Hi2)
Temperature sensor #1 (connected to
SM-Temp 1 and set as Ambient)
sensing temperature higher than high
temperature threshold 2.
Check why temperature is high or
low.
SMTemp1 Temp1 High 1
(SMTemp1 T1 Hi1)
Temperature sensor #1 (connected to
SM-Temp 1 and set as Ambient)
sensing temperature higher than high
temperature threshold 1.
SMTemp1 Temp1 Low
(SMTemp1 T1 Low)
Temperature sensor #1 (connected to
SM-Temp 1 and set as Ambient)
sensing temperature lower than low
temperature threshold.