Brochures and Data Sheets
NetSure
™
ACU+ Controller (Advanced Control Unit Plus)
User Instructions, UM1M820BNA (Issue AK, March 3, 2014)
Spec. No: 1M820BNA, 1M820DNA Code: UM1M820BNA
Model No: M820B, M820D Issue AK, March 3, 2014
29
5. Click the “Browse….” button and navigate to the folder
where the file is located. Select the file and then click the
“Download” button. Click “Start Controller” to restart the
Controller with the downloaded file installed.
Reloading the Configuration Package Stored in the ACU+
Controller (Restoring Defaults)
This procedure is typically used to restore any changes you made
to any settings, relay assignments, alarm severities, signal names,
or PLC expressions. This file is not shipped with the system. There
are one or two steps required to restore your ACU+ as shipped.
• One step to reload the ACU+ configuration package
(required only if you made any changes to relay
assignments, alarm severities, signal names, or PLC
expressions).
• One step to reload the "SettingParam.run" file (required
only if you made any setting changes like float/ equalize
voltage or alarm thresholds).
Your system may have been configured for specific
options at the factory which creates a
“SettingParam.run” file. Reloading the configuration
(restoring defaults) will return the system to the settings
of the default configuration package. These are the
settings before specific options may have been
configured by the factory. To restore the system to the
settings as shipped, after reloading the configuration
(restoring defaults), you must reload the factory
provided “SettingParam.run” file.
Note:
If a system was shipped with factory modified settings,
the system is supplied with a USB memory device that
contains a “SettingParam.run” file as shipped. The
“SettingParam.run” file has a seven-digit UIN (Unique
Identification Number) preceding the “SettingParam.run”
filename. The UIN identifies a “SettingParam.run” file for
use with a specific system. This file can be used to restore
your system to the configuration as shipped. Refer to
“Reloading a Backed-Up ACU+ Configuration” on page 27
to reload the supplied “SettingParam.run” file.
PROCEDURE
WARNING! When this procedure is performed, the
Controller’s existing configuration and parameter
settings will be lost. The “SettingParam.run” file is
deleted. Before reloading the configuration (restoring
defaults), save the “SettingParam.run” file (see Backing
Up the ACU+ Configuration on page 26).
AFTER PERFORMING THIS PROCEDURE, RELOAD THE
“SETTINGPARAM.RUN” FILE AND CONFIGURATION PACKAGE, IF
REQUIRED.
Local Menu Navigation:
Main Menu / Settings / Controller / Reload Config.
The only selection for "Reload Config" is Yes. Once Yes is selected
and confirmed, the configuration package stored in the ACU+
Controller is reloaded into memory. All settings WILL BE restored
to the factory defaults of the configuration package.
WEB Menu Navigation:
Maintenance / Restore Factory Defaults / select “Restore Defaults”.
See also “Restore Defaults Sub-Menu” on page 132.
Rebooting the Controller
Local Menu Navigation:
Press ENT and ESC at the same time to reset the ACU+ Controller.
WEB Menu Navigation:
Maintenance / Restore Factory Defaults / select “Reboot
Controller”.
Note:
After rebooting, you must exit your browser and re-login to see
any changes made.
Spec. No. 588820300 Battery Rack System (Lithium Ion Battery
Configuration)
When the ACU+ is equipped with the Lithium Ion Battery
Configuration for use with Spec. No. 588820300 NetSure™ Battery
Rack System, the only required settings for battery functions is the
float voltage and ABCL (Active Battery Charge Current Limit) point.
Note:
The maximum value that the ABCL point can be adjusted to is
60A, which is below the maximum current the battery can
handle.
The batteries communicate their status and alarms to the ACU+.
The ACU+ displays these via the LCD and WEB interfaces.
Batteries are added to the ACU+ inventory as they are detected. If
a battery communications cable is removed, a Li-Ion Battery
Communication Fail alarm is generated. If the controller resets
while a Li-Ion Battery Communication Fail alarm is active, the alarm
changes to a Li-Ion Battery Lost alarm. If you clear any of these
alarms, that battery is removed from the ACU+ inventory.
Setting SNMP Parameters
Local Menu Navigation:
none.
WEB Menu Navigation:
Maintenance / NMSV2 Configuration and NMSV3 Configuration.
Warning