Brochures and Data Sheets
NetSure
™
ACU+ Controller (Advanced Control Unit Plus)
User Instructions, UM1M820BNA (Issue AK, March 3, 2014)
Spec. No: 1M820BNA, 1M820DNA Code: UM1M820BNA
Model No: M820B, M820D Issue AK, March 3, 2014
25
WEB Menu Navigation:
Device Information / Battery Group / Control Tab.
Clearing Logs
Local Menu Navigation:
Main Menu / Settings / Alarm Setting / Alarm Param / Clr Alm Hist.
The only selection for "Clr Alm Hist" is Yes. Once Yes is selected and
confirmed, the alarm history log is cleared.
WEB Menu Navigation:
Maintenance / Clear Data.
Select which log to clear (“Alarm History”, “Data History”, “Control
Command Log”, “Battery Test Log”, “System Runtime Log”, or
“Diesel Test Log”). Select “Clear”.
Clearing the Maintenance Alarm
A maintenance time can be set which, once expires, issues a
maintenance alarm. When the maintenance alarm is issued,
perform the routine maintenance and reset the maintenance
timer. To reset the maintenance timer and clear the Maintenance
Alarm, clear the Maintenance Run Time.
Local Menu Navigation:
Place Controller in Manual Mode, then Main Menu / Manual /
Power System / Clr MtncRunTime.
The only selection for "Clr MtncRunTime" is Yes. Once Yes is
selected and confirmed, the maintenance timer is reset and the
maintenance alarm is cleared.
Place Controller back to Auto mode.
WEB Menu Navigation:
Quick Settings / “Auto/Manual” Setting / change to Manual.
then
Device Information / Power System / select the Control Tab and
clear the maintenance timer.
then
Quick Settings / “Auto/Manual” Setting / change to Auto.
Viewing the ACU+ Controller’s Device Inventory
Local Menu Navigation:
Main Menu / Status / Sys Inventory.
WEB Menu Navigation:
Maintenance / System Inventory.
Updating the ACU+ Controller’s Device Inventory
Local Menu Navigation:
Main Menu / Settings / Controller / Auto Config.
The only selection for "Auto Config" is Yes. Once Yes is selected and
confirmed, the ACU+ Controller will auto-configure for the devices
connected to it.
WEB Menu Navigation:
Configuration / Auto Configuration.
Blocking Alarms
Local Menu Navigation:
Main Menu / Settings / Alarm Setting / Alarm Param / Block Alarm.
or
Main Menu / Settings / Power System / General / Alarm Blocked.
WEB Menu Navigation:
Device Information / Power System / Settings Tab / Outgoing
Alarms Blocked.
Set to:
•
Normal:
Alarms are processed normally.
•
Blocked:
Forces the alarm relays in the "off" state and
blocks alarms from changing the relay state.
Setting Auto Equalize
Local Menu Navigation:
Main Menu / Settings / Battery / Charge / Auto EQ / once enabled,
additional parameters appear.
or
Main Menu / Settings / Battery / Charge / Cyc EQ / once enabled,
additional parameters appear.
or
Main Menu / Quick Setting / “FLT/EQ” Set.
Also set “Maximum EQ Time” in same menu.
WEB Menu Navigation:
Device Information / Battery Group / Settings Tab / Automatic
Equalize. Once Automatic Equalize is enabled, additional
parameters appear.
or
Device Information / Battery Group / Settings Tab / Cyclic Equalize.
Once Cyclic Equalize is enabled, additional parameters appear.
or
Quick Settings / “Float/Equalize” Settings / once Automatic