Brochures and Data Sheets
NetSure
™
ACU+ Controller (Advanced Control Unit Plus)
User Instructions, UM1M820BNA (Issue AK, March 3, 2014)
Spec. No: 1M820BNA, 1M820DNA Code: UM1M820BNA
Model No: M820B, M820D Issue AK, March 3, 2014
24
Programming the Audible Alarm Feature
Local Menu Navigation:
Main Menu / Settings / Alarm Setting / Alarm Param / Alarm Voice.
Set "Alarm Voice" to:
•
On:
When a new alarm occurs, the audible alarm sounds.
Press any key to silence the audible alarm.
•
Off:
Disables the audible alarm.
•
3 minutes / 10 minutes / 1 hour / 4 hours:
When a new
alarm occurs, the audible alarm sounds. The audible
alarm automatically silences after the selected time
period.
WEB Menu Navigation:
none.
Adding, Deleting, and Modifying Users
Local Menu Navigation:
none.
WEB Menu Navigation:
Refer to “User Information Settings Sub-Menu” on page 129.
Assigning Severity Level to Alarms
Local Menu Navigation:
Main Menu / Settings / Alarm Setting / Alm Severity.
WEB Menu Navigation:
Configuration / Signal Information Modification / select entry from
“Query Device Type” list / select “Alarm Signal” from “Signal Type”
list / select entry from “New Level” list / press “Set”.
Assigning Relays to Alarms
Local Menu Navigation:
Main Menu / Settings / Alarm Setting / Alarm Relay.
WEB Menu Navigation:
Configuration / Alarm Relays / select entry from “Standard
Equipment” list / select entry from “New Relay Number” list / press
“Modify”.
Changing the Names of Items Displayed in the LCD and Web-
Interface Menus
Note:
Only relay names and digital input names are recommended
to be changed for troubleshooting purposes.
Local Menu Navigation:
none.
WEB Menu Navigation:
Configuration / Equipment Info Modification.
Configuration / Signal Information Modification.
Viewing Alarms
Local Menu Navigation:
Main Menu / Status / Active Alarms.
WEB Menu Navigation:
Active alarms are listed in the lower right window pane. If the
window pane is collapsed, click the "arrow" icon to expand the
alarm list.
Clearing Rectifier Lost, Rectifier Communication Fail,
Converter Lost, Converter Communication Fail, and All
Converter Comm Fail Alarms
Navigate to the menus to clear the respective alarm as indicated
below.
Local Menu Navigation:
Main Menu / Manual / Rectifier / All Rect Ctrl.
Main Menu / Manual / Converter / All Conv Ctrl.
WEB Menu Navigation:
Device Information / Rectifier Group / Control Tab.
Device Information / Converter Group / Control Tab.
Clearing SMTemp Lost and SMTemp Probe Alarms
Navigate to the menus to clear the respective alarm as indicated
below.
Local Menu Navigation:
Main Menu / Manual / SMTemp / SMTemp Group.
Main Menu / Manual / SMTemp / SMTemp #.
WEB Menu Navigation:
Device Information / SM Temp Group / Control Tab.
Device Information / SM Temp Group / SM Temp # / Control Tab.
Clearing Battery Alarms
Navigate to the menus to clear the respective alarm as indicated
below.
Local Menu Navigation:
Main Menu / Manual / Batt Group.