Brochures and Data Sheets
NetSure
™
ACU+ Controller (Advanced Control Unit Plus)
User Instructions, UM1M820BNA (Issue AK, March 3, 2014)
Spec. No: 1M820BNA, 1M820DNA Code: UM1M820BNA
Model No: M820B, M820D Issue AK, March 3, 2014
22
password, with the cursor at the User Name field (default
is “Admin”), press the down arrow key to move cursor
down to the password line. Press
ENT
. “0” is highlighted.
Press the up arrow key once to change the “0” to”1”
(default password is “1”), then press
ENT
twice. (
Note:
If
you have been assigned a unique User Name and password,
follow this procedure to enter these.)
3. With the Settings menu screen displayed, navigate to
and select “
Converter
” (ENT).
4. Navigate to “
Conv #
” (# is used here to represent the
converter identification number). Press
ENT
. The
converter # menu screen is displayed, and the green LED
on one converter starts flashing. This is the converter
currently identified by the ACU+ as converter #. (If this is
not the converter you want, press
ESC
to return to
converter menu screen and select a different converter.)
5. Navigate to and select “
Set Conv ID
”. Press
ENT
. Use the
up or down keys to change the ACU+ identification
number for the flashing converter. Press
ENT
.
6. Press
ESC
to return to converter menu screen.
7. Navigate to and select the next converter.
8. Repeat steps 4) through 7) for each of the remaining
converters in the system.
9. When you have finished selecting identification numbers
for all converters, repeatedly press
ESC
to return to the
Main Menu.
10. Navigate to and select “
Manual
” (ENT) / “
Converter
”
(ENT) / “
All Conv Ctrl
” (ENT).
11. Navigate to “
Confirm ID
”. Press
ENT
. “
Yes
” highlights.
12. Press
ENT
to select the operation. Press
ENT
again to
confirm.
Note:
Check you numbering to be sure it is correct. If there
where conflicts in your numbering, converters with
conflicts will be assigned the next available sequential
number.
13. Return to the Main screen by repeatedly pressing
ESC
(escape).
Setting Digital Inputs
Local Menu Navigation:
Main Menu / Settings / Power System / General / DI[number] Alarm
State.
WEB Menu Navigation:
Device Information / Power System / Settings Tab / DI[number]
Alarm State.
Setting Battery Block and Battery Midpoint Monitoring (if
equipped with an EIB Assembly)
Local Menu Navigation:
Main Menu / Settings / EIB / EIB 1 / enter the following parameters.
WEB Menu Navigation:
Device Information / EIB Group / EIB 1 / select the Settings Tab and
enter the following parameters.
Parameters
• Voltage Type
• Blk V Diff(12V) or Blk V Diff(Mid)
• Block In-Use
Setting External Shunts (connected to the EIB Assembly)
Local Menu Navigation:
Main Menu / Settings / EIB / EIB1 / enter the following parameters.
WEB Menu Navigation:
Device Information / EIB Group / EIB 1 / select the Settings Tab and
enter the following parameters.
Parameters
• Shunt # Set As (Not Used, General, Load, Battery)
a. Not Used: Indicates this shunt input is not used.
b. General: Indicates the measurement of the shunt
will be displayed and will not be added to Total DC
Load or Total Battery Load.
c. Load: Indicates the measurement of the shunt will
be displayed and added to the Total DC Load.
d. Battery: Indicates the measurement of the shunt
will be displayed and added to the Total Battery Load
and used with Battery Management.
• Shunt # Current
• Shunt # Voltage
Setting External Shunts (connected to the SM-DU+ Assembly)
Local Menu Navigation:
none.