Brochures and Data Sheets
NetSure
™
ACU+ Controller (Advanced Control Unit Plus)
User Instructions, UM1M820BNA (Issue AK, March 3, 2014)
Spec. No: 1M820BNA, 1M820DNA Code: UM1M820BNA
Model No: M820B, M820D Issue AK, March 3, 2014
18
Common Tasks Performed via the
Local Keypad and/or Web Interface
Note:
Ensure current configuration is backed up prior to changing
settings (see Backing Up the ACU+ Configuration on page 26).
Create new backup files after every successful update for your
records and in case of controller failure.
Refer also to “Local Display Menus” on page 75 and “WEB Interface
Menus” on page 102.
Procedures
Changing the Local LCD Display Contrast
Local Menu Navigation:
To change the contrast of the LCD display, from the Main Screen,
press and hold the
Up Arrow
(for increasing) or
Down Arrow
(for
decreasing) then press and hold
ENT
until contrast is as desired.
Release both buttons.
WEB Menu Navigation:
none.
Disabling the Local Keypad Sound
Local Menu Navigation:
Main Menu / Settings / Controller / Keypad Voice.
To disable the keypad sound, set "Keypad Voice" to "Off".
WEB Menu Navigation:
none.
Changing the Date
Local Menu Navigation:
Main Menu / Settings / Controller / Date.
After selecting Date (by pressing
ENT
when the cursor is in the Date
field), use
and
to select the year then press
ENT
, next use
and
to select the month then press
ENT
, and finally use
and
to select the day then press
ENT
.
WEB Menu Navigation:
Maintenance / Time Sync.
Changing the Time
Local Menu Navigation:
Main Menu / Settings / Controller / Time.
After selecting Time (by pressing
ENT
when the cursor is in the
Time field), use
and
to select the hour then press
ENT
,
next use
and
to select the minute then press
ENT
, and
finally use
and
to select the second then press
ENT
.
WEB Menu Navigation:
Maintenance / Time Sync.
See “Time Sync Sub-Menu” on page 137.
Setting IP Communications Parameters
See also Setting IP Communications Parameters on page 14.
Local Menu Navigation:
Main Menu / Settings / Communication / enter parameters.
WEB Menu Navigation:
Maintenance / Network Configuration / enter parameters.
Viewing/Changing the Float Voltage Setting
Local Menu Navigation:
Main Menu / Settings / Battery / Charge / Float Voltage.
or
Main Menu / Quick Setting / “FLT/EQ” Voltag / Float Voltage.
WEB Menu Navigation:
Device Information / Battery Group / Settings Tab / Float Charge
Voltage.
or
Quick Settings / “Float/Equalize” Charge Voltage.
Viewing/Changing the Equalize Voltage Setting
Local Menu Navigation:
Main Menu / Settings / Battery / Charge / EQ Voltage.
or
Main Menu / Quick Setting / “FLT/EQ” Voltag / EQ Voltage.
WEB Menu Navigation:
Device Information / Battery Group / Settings Tab / Equalize
Charge Voltage.
or
Quick Settings / “Float/Equalize” Charge Voltage.
Setting Battery Parameters
Local Menu Navigation:
Main Menu / Settings / Battery / Battery # / enter parameters.
WEB Menu Navigation:
Device Information / Battery Group / Battery # / select the Settings
Tab and enter parameters.