Brochures and Data Sheets
NetSure
™
ACU+ Controller (Advanced Control Unit Plus)
User Instructions, UM1M820BNA (Issue AK, March 3, 2014)
Spec. No: 1M820BNA, 1M820DNA Code: UM1M820BNA
Model No: M820B, M820D Issue AK, March 3, 2014
152
Table 6
Ident Group Controller Ident Group
psStatusBatteryMode
The status of battery modes.
(1) unknown
(2) FloatCharging
(3) ShortTest
(4) EqualizeChargingForTest
(5) ManualTesting
(6) PlanTesting
(7) ACFailTesting
(8) ACFail
(9) ManualEqualizeCharging
(10) AutoEqualizeCharging
(11) CyclicEqualizeCharging
(12) MasterEqualizeCharging
(13) MasterBatteryTesting
R
SM Series Group Supervisory Module Group
psSMACNumber The number of SM AC module. R
psSMBATNumber The number of SM BAT module. R
psSMIONumber The number of SM IO module. R
Alarm Trap Group Controller Alarm Trap Group
alarmLastTrapNo The sequence number of last submitted alarm trap. R
alarmTrapTable
(alarmTrapEntry)
Table holding information about the submitted alarm traps. alarmTrapEntry is
the entry (conceptual row) in the alarmTrapTable.
R
alarmTrapNo The unique sequence number of this alarm trap. R
alarmTime
Date and time when event occurred (local time), including timezone if
supported by Controller.
R
alarmStatusChange
The type of alarm change. One of...
(1) activated
(2) deactivated
R
alarmSeverity
The severity of the alarm. One of...
(1) warning - OA, lowest level of alarm severity
(2) minor - A3
(3) major - MA
(4) critical - CA, highest level of alarm severity
R
alarmDescription Free-text description of alarm. R
alarmType Alarm type, i.e. an integer specifying the type of alarm. R