ACU+ Controller (Advanced Control Unit Plus)
User Instructions, UM1M820BNA (Issue AK, March 3, 2014)
Spec. No: 1M820BNA, 1M820DNA Code: UM1M820BNA
Model No: M820B, M820D Issue AK, March 3, 2014
151
Table 6
Ident Group Controller Ident Group
System Group Controller System Value Group
systemStatus
Status of the complete plant (highest alarm). One of...
(1) unknown - status has not yet been defined
(2) normal - there are no activated alarms
(3) warning - OA, lowest level of 'abnormal' status
(4) minor - A3
(5) major - MA
(6) critical - CA, highest level of 'abnormal' status
(7) unmanaged
(8) restricted
(9) testing
(10) disabled
R
systemVoltage System voltage, stored as mV. R
systemCurrent System current, stored as mA. R
systemUsedCapacity Used capacity, stored as percentage of the total capacity . R
psBattery Group Power System Battery Group
psBatteryVoltage Battery voltage, stored as mV. R
psBatteryCurrent Battery current, stored as mA.
R
psInput Group Power System Input Group
psInputLineAVoltage The AC line A voltage, stored as mV. R
psInputLineBVoltage The AC line B voltage, stored as mV.
R
psInputLineCVoltage The AC line C voltage, stored as mV. R
psTemperature Group Power System Temperature Group
psTemperature1 The first route temperature, stored as 0.001 Celsius degree.
R
psTemperature2 The second route temperature, stored as 0.001 Celsius degree. R
psStatusCommunication
The status of communication with the Power System.
(1) unknown
(2) normal
(3) interrupt indicates some errors occurred between Power System and agent
R