User Instructions, UM1M820BNA (Issue AK, March 3, 2014)
Spec. No: 1M820BNA, 1M820DNA Code: UM1M820BNA
Model No: M820B, M820D Issue AK, March 3, 2014
145
PLC Sub-Menu
Allows you to configure the PLC functions of the Controller.
The following shows the PLC sub-menu.
Operation
The PLC function normally runs every 10 seconds. It starts by executing the first line and stores the result in the output signal/register.
Then executes the next line and continues executing line by line until it reaches the end. The PLC function will be stopped if the ACU+ is
set to Manual Mode.
PROCEDURE
1. Click the ADD button and the window below is shown.