Signal Information Modification Sub-Menu
Here you can change the name of signals connected to the Controller. Signals have two names. One is the “Signal Full Name” and
another is the “Signal Abbreviated Name”. The “Signal Full Name” is displayed in the WEB Interface menus and the “Signal Abbreviated
Name” is displayed in the local LCD display menus.
Enter the new signal name in the “New Name” column and select what Name is to be changed (“Signal Full Name” or “Signal Abbreviated
Name”). Click on the "Set" button to save the new name.
Signal Full Name (32 characters maximum).
Signal Abbreviated Name (15 characters maximum).
Note:
If a signal is renamed it is recommended to retain enough information about the physical location of the signal as possible. As an
example, if you want to assign a name of 'Intrusion 6' to the signal who's default name is 'DI1 Alarm' it could be labeled 'DI1 Intrusion 6'.
This will help in physically locating the wiring etc. related to the 'Intrusion 6' alarm. Alternately, the customer could label the wiring
and/or position that is related to the signal name.
Sample Signal Name Modification Procedure
The following procedure demonstrates how to change the “System Voltage” to “Bus Voltage”.
1. Select the equipment to which this signal belongs: Power System.
2. Select the signal type to which the signal belongs: Sample Signal.
3. Enter new signal name: Bus Voltage.